70
Specific Specifications in MAX/MIN mode
:
Accuracy: add 1% R to the values of the previous table
Capture of the extreme: approximately 100ms.
4.2.12 Active DC Power Measurements
Measurement
Range (2)
0 to
9999W
10.00 to
99.99kW
100.0 to
999.9kW
1000 to
3000kW (1)
Specified
Measurement
Range
1 to 100% of the
measurement range
0 to 100% of the
measurement range
Accuracy (3)
1000A
± (2% R +10cts)
1000 to 2000A
± (2.5% R +10cts)
2000 to 2500A
DC
± (3.5% R +10cts)
2500 to 3000A
DC
± (4.5% R +10cts)
1000A
± (2% R +3cts)
1000 to 2000A
± (2.5% R +3cts)
2000 to 2500A
DC:
± (3.5% R +3cts)
2500 to 3000A
DC:
± (4.5% R +3cts)
Resolution
1W
10W
100W
1000W
Note (1)
- Display of OL or ± OL
- Above 1500kW in single-phase (1000V x 1500A).
Note (2)
Any applied voltage greater than 1000V causes the emission of an
intermittent alarm beep to report a dangerous overload.
Note (3)
The measurement result may be affected by an instability linked to the
current measurement (approximately 0.1A).
Example:
For a power measurement made at 10A, the instability of the
measurement will be 0.1A/10A or 1%.
4.2.13 Active AC Power Measurements
Measurement
Range (2) (4)
5 to
9999W
10.00 to
99.99kW
100.0 to
999.9kW
1000kW (1)
Specified
Measurement
Range
1 to 100% of the
measurement
range
0 to 100%
of the measurement range
Accuracy (3)
1000A
± (2% R +10cts)
1000A
± (2% R +3cts)
Resolution
1W
10W
100W
1000W
Note (1)
- Display of OL above 1000kW in single-phase (1000V x 1000A).
- Bandwidth in AC in voltage = 3 kHz, in current = 2 kHz
Notes (2) and (3)
of the previous § apply.
Summary of Contents for 407
Page 1: ... 32 5 03 21 0 7 5 8VHU 0DQXDO 1 6 ...
Page 2: ... ...
Page 47: ...47 4 In the Bluetooth Devices window select Add ...