5) To program a new Master Code to replace the old one. See “

Record A Master Code

 

stated at 

“Location 01” for the details.

NOTE:

The keypad will set itself to normal operation mode 1 minute after power-up if the Egress Button is 

not pressed and the DAP code is not keyed in. To set keypad back to power-up mode, repeat 

procedures 1-4.

SYSTEM REFRESHING WITH “REFRESHING CODE” --- 9 9 9 9                        

       

The keypad can be refreshed by cleaning all the programmed old data and set it back to default 

values except the

 Master Code

.

      
              

         

     

REFRESHING CODE                          VALIDATION

   

NOTE:

a) 
b) 
c)

 

15

Make sure that system refreshing is really required before entering the refreshing code.
Refreshing takes few minutes. The status LED (amber) keeps flashing during refreshing.
The keypad is back to its default value after refreshing. Re-program of the desired values are 

necessary.

46

SYSTEM  

CODES

FUNCTION

CODE ENTRY

RESULTS

0 0 0 0

system in programming Mode at the first

Factory Set Master Code for User to set 

time.

THIS IS NOT A PERMANENT SYSTEM 

CODE & IT IS CHANGED IF A NEW 

MASTER CODE IS PROGRAMMED.

  

OR

 NEW MASTER CODE  

  

System in 

Programming Mode

9 9 9 9

REFRESH CODE

 -- Refresh the system 

and set all its function back to default 

values.

 

All programmed 

data are cleared 

and back to the 

default values 

except the Master 

Code

2 8 2 8

DAP CODE

-- Direct access to 

programming mode. Valid only in the 

power-up delay period

 

System in 

Programming Mode

0 9 9 9

USER Codes / Cards whole group 

clearing Code for the selected Location

LOCATIONS

:

10--- User Group 1

20--- User Group 2

40--- Vistor Group

41--- Duress Group 1

42--- Duress Group 2

 LOCATION NO.  

  

Whole group 

of users in the 

selected location 

are cleared

* *

Exit Programming Code



The system back 

to normal opration 

after programming

DIRECT ACCESS TO PROGRAMMING MODE WITH “DAP” CODE -- 2 8 2 8             

 

              

In case the Master Code is forgotten, apply the following procedures precisely to set keypad 
into programming mode with DAP code:

1) 

2) 

 

3) 

4) 

Switch OFF all the power for 1 minute to ensure that the keypad is fully discharged.

Switch ON power again. The keypad is in Power-up Mode for 1 minute. The buzzer gives 

continuous beeps and the Status LED is flashing. This is the only time frame to accept the DAP 

code.

Press the Egress Button (the button connecting accross EG IN, (Terminal 11) and (-)GND, 

(Terminal 12) once to enable the keypad for accepting DAP code. The power-up beep stops after 

the Egress Button is pressed.

Key in the DAP code                    and validate it with             (or             ). The Status LED is 

ON and the keypad is in programming mode like using Master Code. It is ready to accept new 

programming data as long as you like until exit programming mode.

PRESS ONCE

EGRESS BUTTON                      DAP CODE                        VALIDATION

Pacifier Tone ON-OFF

7 1

FUNCTION MODE:

0---NO Notification

2---2 Short Beeps

1---1 Second Long Beep

FUNCTION MODE:

0---OFF

1---ON

FUNCTION MODE:

0---OFF

1---ON

 

FUNCTION MODE

 

Mode = 1, 

ON

7 2

Output Announcer

 

FUNCTION MODE

 

7 3

Standby LED Flashing

 

FUNCTION MODE

 

Mode = 1, 

Flashing ON

Mode = 1

 

1 Second 

Long Beep

Pacifier Tone  

8 0

Door Forced Open 

Warning & Time

FUNCTION MODE / TIME:

0---OFF

1-999 Seconds

 

FUNCTION / TIME

 

Mode = 0, 

Door Forced 

Open

Warning OFF

8 1

Propped-up Warning & 

Time

 

FUNCTION / TIME

 

Mode = 0, 

Propped-up 

Warning OFF

9 0

Egress Delay Warning

 

CODE 1

 

CODE 2

 

Mode = 1 

Momentary, 

No warning

TIME = 0

No Delay

9 4

Operation Mode 

FUNCTION MODE: 

 

MODE

 

Mode = 0 

Keypad 

Mode

1---Server Mode

0---Keypad Mode

CODE 1 

FUNCTION 

MODE:

1---Momentary, No warning

2---Momentary, with 

warning

3---Momentary, with 

w Alarm

4---Hold Contact, No 

warning

5---Hold Contact, with 

warning

6---Hold Contact, with 

w Alarm

CODE 2 

DELAY TIME:

 

0---No Delay

1-99 Seconds

Summary of Contents for DK-2836A

Page 1: ...B User Manual MK II FOR ELECTRIC LOCK INTER LOCK AND SECURITY SYSTEM INSTALLATIONS AEI PROTECT ON SYSTEMS LIMITED www apo hk com Ver 201710_V5 VANDAL RESISTANT TRI TECH ACCESS CONTROL KEYPAD WITH CAR...

Page 2: ...User Code Common User Codes for Output 1 2 User Codes Card For Output 1 2 Examples Programming And Operation Visitor Codes For Output 1 Only Duress Codes For Outputs 1 2 Operation And Function of The...

Page 3: ...means that no electricity is connected to it It is prepared for free connections The Relay Output contacts provided in this keypad system are dry contacts N C Normally Closed the contact is closed cir...

Page 4: ...k Actuation Control Output Relay 2 2A Rating N C N O Contacts for External Door Bell Actuation Control A member of the Tri Tech series keypads compatible with the optional controllers reader keypads f...

Page 5: ...to ground when duress code is entered You may use it to turn ON an LED lamp and or a small buzzer to notify a guard or connect it to a 24 hour Normally Open protection zone of an alarm system Only on...

Page 6: ...net Housing Die Cast Zinc Alloy Protection Bracket Faceplate Material Stainless Steel APPLICATION HINTS FOR THE AUXILIARY TERMINALS B DOOR SENS With the help of a Normally Closed door position sensor...

Page 7: ...oded operation It is compatible with the auxiliary readers AR 2802 and the auxiliary reader keypads AR 2806 AR 2807 AR 2809 Total 3 auxiliary readers or reader keypads can be connected in parallel wit...

Page 8: ...ith all the input and output installations connecting to it The DK 2836 manages the data in the system with its Data I O Bus The decoder operates the door lock and the appliances directly according to...

Page 9: ...o open during the operation While one of the doors is opened the other door keeps close until the open door is re closed It prevents the unauthorized people dashing into a protected area while the doo...

Page 10: ...ormation 14 DATA I O Data Input Output Communication Bus Data I O port is prepared for setting up a data bus for the connection of the auxiliary reader keypads and the split decoder in system expansio...

Page 11: ...essful Key Entry 1 Beep 1 Flash 3 Successful Code Card Entry 2 Beeps 2 Flashes 4 Unsuccessful Code Card Entry 5 Beeps 5 Flashes 5 Power Up Delay Continuous Beeps Continuous Flashes 6 Output Relay Acti...

Page 12: ...r Code Operation Media 3 A secondary user code can be repeatedly used for a group of cards in a department Owner can make a proprietary department code for each department in a company Only the staff...

Page 13: ...o open the door Card with proprietary user code approach is ideal for the area that high security is the main concern This operation mode can also report Duress Alarm by keying in the duress code inst...

Page 14: ...gned for setting the keypad to programming mode with DAP code See the details of DAP CODE 2 8 2 8 below 1 The keypad gives continuous beeps for 1 minute after power up 2 The power up delay can be stop...

Page 15: ...to normal opration after programming DIRECT ACCESS TO PROGRAMMING MODE WITH DAP CODE 2 8 2 8 In case the Master Code is forgotten apply the following procedures precisely to set keypad into programmi...

Page 16: ...system program It can not be changed in any ways 16 45 PROGRAMMING SUMMARY CHART LOCATION FUNCTION ENTRY LIMITS CODE OPTIONS CODE ENTRY FACTORY DEFAULT 0 1 Master Code 4 8 Digits MASTER CODE NIL 0 2...

Page 17: ...used with the EM Card It is for example here only f Confirm the Card Code is stored 2 beeps 6 Record an EM Card Commom User Code to Operate The Output 1 for Door Open a b c d e a 10 Programming Locat...

Page 18: ...eps 3 2 8 9 is a Master Code for example here only It replaces the old master code 0000 OPERATION AND FUNCTIONS OF THE SUPER USER CODE 1 Operate Output 1 and 2 The operation of the Super User Code is...

Page 19: ...ops in toggle with the following code entry It can be done before or during the inhibition period Door Lock Operation Resumes Start Stop in Toggle NOTE The INHIBIT LED Red is ON in inhibition and turn...

Page 20: ...ep confirms the entry EXAMPLES Example 1 Set Egress Button in Momentary contact of 5 seconds with delay warning beep a b c d a Egress function programming b Momentary contact with warning c Delay time...

Page 21: ...ber to enable 1 of the 6 configurations described below Momentary Contact Mode without Warning Default Momentary Contact Mode with Warning Beep Momentary Contact Mode with Warning Beep Alarm Holding C...

Page 22: ...peration mode a b a Key in the Private User Code 1 2 3 4 b Confirm it with the key Output 2 activates Read Card Read Card 22 High Traffic Passage A short buffer time may be necessary for opening a doo...

Page 23: ...e to prevent unattended leaving shoplifting and unauthorized use of the emergency exits The Intelligent Egress Button can be programmed to do something to get attention from the person on duty before...

Page 24: ...f users including the Codes and Cards can be cleared with the following command a b c a The User Group 1 10 is selected to be cleared 20 for Group 2 b Key in the Group Deletion Command 0 9 9 9 c Confi...

Page 25: ...ation 72 1 LOCATION Key in Location 2 FUNCTION MODES FOR OUTPUT ANNOUNCER Output announcer gives notification beep on the operation status of the outputs There are two notification modes available for...

Page 26: ...all User Codes must be in 5 digits as well All other User Codes not in 5 digits become invalid When the number of digits reaches the system will check the User Code automatically Good for high traffic...

Page 27: ...e code entry The Duress Codes MUST be in the same digit length with the Master Code for Auto Mode code entry Always set a Duress Code that is easy to remember in Panic Situation Only one number differ...

Page 28: ...or Output 1 b Duress Code ID c The Duress Code e Entry Confirmation iii Pause the real time inhibition manually The real time inhibition can be stopped temporarily if require such as the staff work ov...

Page 29: ...ent in emergency START STOP TIMES FOR DAILY INHIBITION OF OUTPUT 1 Location 56 Setting with start and stop times into the keypad the real time inhibition period for output 1 will recycle daily until t...

Page 30: ...4 hour real time clock provides the daily time base for starting and stopping the function of inhibition to relay output 1 mainly for electric door lock strike No real time clock setting is required i...

Reviews: