13 : DOOR SENS (Door Position Sensing Input -- Normally Close)
A Normally Closed (N.C.) sensing point referring to (-) ground, with the help of a normally closed
magnetic contact monitors the open or close status of the door. It initiates the following functions for
the system. Connect it with jumper to (-) Ground if not used.
a) Door Auto Re-lock
The system immediately re-locks the door after it is re-closed before the end of the programmed time
for output 1. It prevents unwanted “tailgate” entry.
b) Door Forced Open Warning
The keypad generates “door forced open” warning instantly once the door is forced to open without
a valid user Code, Card or egress button. The warning lasts as long as the time programmed (1-999
sec). It can be stopped with an User Code or card for output 1 at anytime. See programming Location
80 for the details.
c) Door Propped-up Warning
The keypad generates propped-up warning beeps while the door is left open longer than the
allowable time programmed. The warning will last as long as the door is open until re-closed. See
programming Location 81 for the details.
d) Inter-lock Control
The inter-lock control output always goes to (-) while the door is open, which gives signal to disable
the partner keypad in an inter-lock system. See the Inter-lock terminal 10 description for more
information.
14 : DATA I/O (Data Input/Output Communication Bus)
Data I/O port is prepared for setting up a data bus for the connection of the auxiliary reader-keypads
and the split-decoder in system expansion. See the examples in “Application Expansions” section for the
details.
15 - 16 : TAMPER N.C. (Tamper Switch Normally Closed Contact)
A normally closed dry contact while the keypad is secured on its box. It is open while keypad is
separated from the box. Connect this N.C. terminal to the 24 hour protection zone of an alarm system
if necessary.
10
51
1) Dual-station Access Control Door Lock
Description
Owner can select an auxiliary reader AR-2802 or an auxiliary reader-keypad AR-2806, AR-2807
or AR-2809 and connect it with the master keypad DK-2836 to expand the system with
dual-station for user convenience. Simply connect the reader or the reader-keypad in parallel
with the Data I/O Bus of the master keypad. The auxiliary reader accepts all the cards that are
programmed in the master keypad. If it is an auxiliary reader-keypad it accepts cards and user
codes like the master keypad.
Note:
Keep
Operation Mode
setting of the keypad in
“Keypad Mode (default)”
with
Location
(–) COMMON GND
(+) POWER SUPPLY
DATA I/O BUS
DK-2836
(MASTER KEYPAD)
AR-2802 S or A
(AUXILIARY READER)
ELECTRIC LOCK
System Connection
94 = 0
in this application.
Wiring Diagram
(–) COMMON GND
(+) POWER SUPPLY
DATA I/O BUS
DATA I/O BUS
AR-2802S AUXILARY READER
OR
AR-2802A
TAMPER
N. C.
(+) (–)
12-24V DC
LED
DATA
I/O
Dual-Station Access Control Door Lock