42
This parameter cannot be changed.
3.3.2.2 Type
This parameter shows the type of device learnt by the panel. For example, this can show Call Point, Multi-
Sensor, ION Smoke, Heat, etc.
This parameter cannot be changed.
3.3.2.3 Value
This parameter shows the analogue value returned by the device. The number displayed will vary according to
the type of device fitted. An ‘H’ (High) and ‘L’ (Low) is shown for logic inputs. This parameter cannot be
changed. For specific device types, the mode of operation / sensitivity band is also shown.
3.3.2.4 Zone
This parameter shows the Zone to which this device has been assigned. Use the
number
keys to change the
zone assigned to the device. Zones used must be unique to this panel.
Meldergruppe Number (Mld)
The Meldergruppe number is only shown on panels for the German market (software specific feature). This is
the assigned device number within the meldergruppe and can be in the range 1
– 32. Use the
number
keys to
change the meldergruppe number assigned to the device.
3.3.2.5 Device Text
This parameter shows the 26-character location text assigned to this device. For guidance on how to change
the text, refer to Section
3.3.2.6 Action
This parameter shows the action that will be performed when this device indicates an active (alarm) condition.
For example:
[Loop 1 Devices] <More>
Address Action Sensitivity O/P
001.0 FIRE SIGNAL DEFAULT
002.0 FIRE SIGNAL DEFAULT
003.0 FIRE SIGNAL DEFAULT
004.0 FIRE SIGNAL DEFAULT
Press the
✔
button to change the action assigned to this input device. A pop-up window is then shown on the
display from which an action can be selected.
[Select New Action]
FIRE SIGNAL .
PRE-ALARM
FAULT SIGNAL
Press the
buttons to scroll through the list of Actions and then press the
✔
button to confirm the change.
The display reverts to the device list showing the new action assigned to this device. Alternatively, press the
‘Esc’
button to cancel the changes and return to the device list display. The following Actions are available.