47
ACCEPT NEW DEVICE
.
REJECT NEW DEVICE
ACCEPT ALL NEW DEVICES
REJECT ALL NEW DEVICES
! Address 002 NEW DEVICE
If the new device is accepted (or all new devices are accepted), the panel will configure the memory to register
these devices. All data will be configured to initial settings for sensitivity threshold changes, text assignments,
zone assignment, action, etc. for these devices.
If the new device is rejected (or all new devices are rejected), the panel clears all programming for these
devices and will not attempt to communicate with the devices at these addresses.
Press the
buttons to highlight the required menu option and then press the
✔
button to confirm. The pop-up
window will disappear and the panel will continue with the auto learn process.
If a single device is accepted / rejected and another new device is subsequently registered, the display will once
again show the pop-up window to accept or reject this device.
3.3.3.4 Procedure if the Panel finds Devices Changed
When the panel finds a new type of device installed at an address previously learnt and programmed in the
panel, the Auto Learn process is suspended and the display shows a pop-up window with options. For example:
ACCEPT NEW DEVICE
.
KEEP OLD DEVICE
ACCEPT ALL NEW DEVICES
REJECT ALL NEW DEVICES
! Address 002 TYPE CHANGE
This situation could arise for example if a heat detector has been installed in place of an optical smoke detector.
If the new device type is accepted (or all new device types are accepted), the panel will configure the memory to
register these devices. All data will be configured to initial settings for sensitivity threshold changes, text
assignments, zone assignment, action, etc. for these devices.
If the new device type is rejected (or all new device types are rejected), the panel remembers the programming
for the original devices. The panel will report a fault condition until such time as the correct device types are
reconnected.
Press the
buttons to highlight the required menu option and then press the
✔
button to confirm. The pop-up
window will disappear and the panel will continue with the auto learn process.
If a single device is accepted / rejected and another new device type is subsequently registered, the display will
once again show the pop-up window to accept or reject this device.
3.3.4 Loop
– Calibrate
Calibrates devices
– Note this can take up to several minutes if many detectors & sounder bases are installed.
3.3.5 Loop - History
Displays basic event history for each device and sub-address.
[History Lp 1 Adrs 001.0 ↓ ]
Last Activation :
Last Test :
Last Disable :
Last Enable :
Created : 12/01/09 09:18:58