www.advancedco.com
Specifications:
Item
Specification Details
Part Number
Ex-3001
Enclosure
Steel IP30, RAL 7035
Dimensions H x W x D mm
330 x 400 x 90
Environmental Class
Class A
– Indoor IP30 0°C to 40°C
Humidity
95 % Max
Weight (excluding batteries)
5.1Kg
Cable Entries (20mm knockouts)
17x top and 13x top rear
Mains Supply
200V-240V (+10%, -15%), 50/60Hz AC, 1.0A max
Power Supply
Imax
24V DC, 3A High Efficiency Switched Mode [2A load, 1A battery charging]
Ripple: 200mV max. (Note: 1V p-p including switching frequency noise)
Imax(a) = 1.2A
1
, Imax(b) = 3.0A
2
Battery Capacity and Battery
Internal Resistance
24V 4Ah Internal (min), 24V 7Ah Internal (max)
1.6Ω
Charging Current
1.0A Temperature Compensated (27.4V DC nominal at 20°C)
Number of Fire Zones
3
Number of Flooding Zones
1
Actuator Output
24V DC, 1.0A suitable for either Metron or Solenoid
Sounder Outputs
3x rated at 1A each programmable
Relay Outputs
4x rated at 1A 30VAC/DC (max) 10mA 5V (min) [2x Fixed
– Fire / Fault, 2x Programmable]
Relay Outputs (Optional)
8x rated at 1A 30VAC/DC (max) 10mA 5V (min) programmable (requires EXP-008)
Key-Switches (Optional)
2x Programmable
External Inputs (Monitored)
7x Fixed (Mode, Manual Trigger, Hold, Abort, Flow Monitor, Valve Monitor, Pressure Monitor)
4x Programmable
AUX Supply Output
24V DC, 0.5A
Communications
RS485 to Remote Status Indicators
Display
Graphic LCD 124x64 dots
LED Indicators
26
Event log
100 Fire / Trigger Events, 500 General Log Events
Standards
EN12094-1:2003, EN12094-3 :2003,
EN54-2:1997 +A1:2006, EN54-4:1997 +A1:2002 +A2:2006, EN54-13 :2005
As our policy is one of constant product improvement the right is therefore reserved to modify product specifications without prior notice
1
The overall capability of the power supply is restricted to panel loading and maximum power available from the AUX outputs. Refer to the
relevant sections of this manual for the minimum and maximum output voltages of each circuit.
2
The charger is turned off in alarm.