www.advancedco.com
6
1.1 EN54 Functions
This Control Panel is compliant with the requirements of EN54-2: 1997 +A1: 2006
and EN54-4: 1997 +A1: 2002 +A2: 2006.
In addition to the basic requirements, the following optional functions are provided
and these comply with the requirements of EN54.
CIE Optional Functions
EN54-2 Clause
Outputs to Fire Alarm Devices
Delays to outputs
Alarm Counter
Total Loss of Power
Test Condition
7.8
7.11
7.13
8.4
10
P.S.E Functions
EN54-4 Clause
Operation from a main power supply
Operation from a standby battery
Monitor and Charge the Standby Battery
Recognise and Notify Supply Faults
5.1
5.2
5.3
5.4
This Fire Alarm Control Panel also supports additional functions that are not covered
by EN54. These are as follows:
Additional Function
Refer to
Paragraphs
Auxiliary Power Supply Output
Auxiliary Relay Outputs
1.1.1
EN54 Optional Features with Requirements
In addition to the mandatory requirements of EN54-2, the Control and Indicating Equipment (CIE) supports the
following optional features with requirements: -
Section 7.8
Outputs to Fire Alarm Devices.
The CIE has provision for connection to Fire Alarm Devices. It is possible to Silence
and Re-sound the alarms at Level 2. Refer to the User Manual for further
information.
Refer to Sections 2.3.5.5 and 3.3.5
for information on installation and output
programming.
Section 7.11
Delays to Outputs.
The CIE has provision for delaying the activation of outputs in response to zone fire
conditions. These delays are programmable on a zone–by–zone basis.
Refer to Section 3.3.1 for information on delay programming.
Section 7.13
Alarm Counter.
The CIE has provision record the number of times that the fire alarm condition is
entered. Refer to the User Manual for further information.