www.advancedco.com
7
Section 8.4
Total Loss of Power.
The CIE has provision to annunciate a total loss of power for one hour. Refer to
Section 3.3.7 for information on configuring this option.
Conditions:
- Requires installation of 7Ah batteries
- The minimum battery operating voltage is 20.4V
- Output Power AUX2 must not be used for external equipment.
- Output Power AUX1 will be switched off when battery voltage is <20.4V
Section 10
Test Condition.
The CIE has provision for testing the installation on a per zone basis. Refer to the
User Manual for further information.
1.2 EN12094 Functions
This Control Panel is compliant with the requirements of EN12094-1: 2003 and
complies with the following mandatory functions:
Reception and processing of input trigger signals (zone inputs and manual trigger)
Transmission of the extinguishing signal (actuator output)
Output to alarm devices
Indication
Transmission of the fault warning and component status conditions
Transmission of the released condition
This control panel incorporates a manual triggering device in accordance with the
requirements of EN12094-3: 2003.
1.2.1
EN12094-1 Optional Features with Requirements
In addition to the mandatory requirements of EN12094-1, the Extinguishing Control Device (ECD) supports the
following optional features with requirements: -
Section
4.17
Delay of Extinguishing Signal.
The ECD has provision to delay the transmission of the extinguishing signal. This can
be programmed in 1-second intervals up to a maximum of 60-seconds. Refer to
Section 3.3.3.1 for programming.
Section
4.18
Monitor Flow of Extinguishing Agent.
The ECD has provision to monitor the flow of the extinguishing agent once released.
One fixed input is provided. Programmable inputs can also be configured as flow
inputs. Refer to Sections 2.3.5.6, 3.3.4 and 3.3.3.1.
Section
4.19
Monitor of Status of Extinguishing Components.
The ECD has the provision to monitor the status of extinguishing components such as
loss of agent, temperature, etc. Refer to Sections 2.3.5.6, 3.3.4 and 3.3.3.1.
Means shall be provided to transmit the information concerning the blocked position
of a manual control device. Refer to sections 2.3.5.1 and 3.3.5 for further information.