www.advancedco.com
34
3.3.7 General Options
The display presents a menu of user general options.
Parameter
Comments / Description
Options
Default
Setting
Level 2 Time Out
The Level 2 Time Out can be configured in the range 0
– 5
minutes (0 = No time out
– stay in Level 2)
After the timeout, the menu functions and user controls are
inhibited. Password entry is required to re-enable these.
0
– 5 Minutes
5 Minutes
Earth Detection
Determines if the panel shall report earth detection faults.
YES/NO
YES
Pressure Inputs
Determines the normal, quiescent state of the contacts
associated with the equipment used to sense loss of
extinguishant pressure (applies to all system inputs used
for pressure loss detection).
Normally Open /
Normally Closed
Normally
Open
Config
Shows the checksum of the configuration memory.
Option to erase the configuration (press the
button).
> Erase
Configuration
N/A
Program
Shows the current program version
Press the
button to show the program checksum.
> Show Checksum
N/A
Log
Determines the information that is recorded in the log.
S Mode also records the return to normal
transitions.
Standard,
S
Standard
Service Number
Determines the telephone contact number that is shown
on the normal display when there is an acknowledged fault
condition.
---
Service Due Date
Determines the date/time at which a fault warning
messages will be displayed to indicate service is overdue.
dd-mmm-yyyy
hh:mm
06-01-2020
10:00
Mute
Determines if the panel permits the buzzer to be muted at
Level 1 or if it can only be muted at Level 2.
LEVEL-1
LEVEL-2
LEVEL-1
Reset Mode
Determines if the user is presented with the choice of
resetting ‘gas only’ or ‘fire & gas’ on a reset , alternativley
no menu is presented and ‘fire & gas’ are always reset.
PROMPT
ALL
PROMPT
Daylight Saving
Used to turn on/ off daylight saving mode
– which
automatically shifts the current time forward/ backwards by
1 hour on programmed days of the year.
YES
NO
YES
EN54-2 [8.4]
Determines if the panel shall annunciate a total loss of
power.
YES
NO
NO
Section 7.6
Reset from the fire alarm condition.
For full compliance with both EN54-2 and EN12094-1 the ‘PROMPT’ option
must be selected for Reset Mode. For compliance with only 12094-1 select the
‘ALL’ option. This option provides a single reset button action to reset the
system (note reset is inhibited during the activation condition).
3.3.7.1 Daylight Saving Options
The display presents a menu of the daylight saving configuration.
Parameter
Comments / Description
Options
Default
Setting
Enabled
Determines whether the daylight saving function is on or
off. On means that the time will be shifted forwards &
backwards by 1 hour, two times a year on the dates
determined below.
YES
NO
YES
Forward Order
Specifies which occurance of the day specified (below) in
the month specified (below) the time will be shifted
forwards by 1 hour (at 2AM the time will change to 3AM).
1
ST
2
ND
3
RD
4
TH
LAST
LAST
Forward Day
Specifies on which day of the week the time will be shifted
forwards by 1 hour.
MON
– SUN
SUN