3.3.9  Enable PC LINK 

The ENABLE PC LINK menu option allows a PC to be connected to the panel for upload / download. 

[USB Port Enabled] 
 
CURRENT STATUS: 
IDLE 
 
 

 

The display shows the current status of the link. Possible 
status messages are: 

LOGO UPDATE 

 

(< PC) 

EVENT DATA TRANSFER 

(> PC) 

CONFIG DATA TRANSGER 

(> PC) 

 

 

NOTE: When this function is enabled and in use, any fault reporting of power supply (PSE) 
fault conditions is temporarily suspended. 

 

3.3.10 Exit 

To exit from the Commissioning / Programming Menu, select the EXIT option and press the 

 button. The 

display prompts for the Level 3 password. 

Summary of Contents for Ex-3001

Page 1: ...www advancedco com Extinguishing Control Panel Installation and Commissioning The operation and functions described in this manual are available from Software Version Ex 3000 V2 05C onwards...

Page 2: ...rogrammable Relay Outputs 4x rated at 1A 30VAC DC max 10mA 5V min 2x Fixed Fire Fault 2x Programmable Relay Outputs Optional 8x rated at 1A 30VAC DC max 10mA 5V min programmable requires EXP 008 Key S...

Page 3: ...ts 16 2 3 5 6 Input Circuits 18 2 3 5 7 Actuator Output Circuit 18 2 3 5 8 USB 19 2 3 5 9 Recommended Cable Routing 20 2 4 KEY SWITCH INSTALLATION 21 2 5 ADJUSTING THE LCD CONTRAST 21 2 6 LOADING CALC...

Page 4: ...ns 37 4 1 3 Quarterly Actions 37 4 1 4 Annual Actions 37 4 2 REPLACEMENT OF COMPONENTS 38 4 2 1 Batteries 38 4 2 2 Liquid Crystal Display 38 5 APPENDICES 39 5 1 APPENDIX 1 FORGOTTEN LEVEL 3 PASSWORD 3...

Page 5: ...oduct has been designed to comply with the requirements of the Low Voltage Safety EMC and the CPD Directives Failure to follow the installation instructions may compromise its adherence to these stand...

Page 6: ...Auxiliary Power Supply Output Auxiliary Relay Outputs 2 3 5 3 2 3 5 1 1 1 1 EN54 Optional Features with Requirements In addition to the mandatory requirements of EN54 2 the Control and Indicating Equi...

Page 7: ...trol panel incorporates a manual triggering device in accordance with the requirements of EN12094 3 2003 1 2 1 EN12094 1 Optional Features with Requirements In addition to the mandatory requirements o...

Page 8: ...ing devices etc Refer to Sections 2 3 5 5 and 3 3 5 These circuits are required to be monitored for fault conditions by the ECD Section 4 26 Triggering Signals to Equipment outside the System The ECD...

Page 9: ...r national standard regulations for fire systems extinguishing system installation for example BS5839 1 2002 BS7273 1 2006 appropriate to the country and location of the installation 1 3 2 Wiring Regu...

Page 10: ...box door chassis assembly and PSE module The chassis is mounted onto the back box via two screws and keyhole mounting holes The screws do not have to be removed to remove the chassis The chassis cont...

Page 11: ...s are installed the ExGo can weigh in excess of 10Kg Use appropriate fixing hardware to secure the panel to the wall For example drill the required holes in the supporting wall using a drill bit diame...

Page 12: ...mains supply via a readily accessible disconnect device Isolation Switch and suitable earth fault protection incorporated in the building installation wiring The Mains cable should be a minimum cable...

Page 13: ...operation Remote LED Connections NOT FITTED ON 1 5A PSE PSE ONLY PSE CHARGER Fit Jumper in required location The unit is supplied as default set for PSE Charger Mode of operation as shown 2 3 5 Extern...

Page 14: ...chassis card the connectors are polarised to prevent incorrect connection Two changeover and six normally open volt free relay outputs are provided Each is rated at 30V AC DC 1A resistive All Relay ou...

Page 15: ...OUNDER DELAYED DISABLE SOUNDER DISABLED FAULT SOUNDER FAULT FIRE SILENCED GENERAL ESC TUV PQRS GHI JKL ABC RESET SILENCE RESOUND MUTE SOUND ALARMS HOLD 2s If using devices that apply a short across th...

Page 16: ...XTINGUISHANT SYSTEMFAULT SOUNDER DELAYED SOUNDER DISABLED SOUNDER FAULT SILENCED ENERAL 1 DETECTION ZONES FIRE FAULT TEST DISABLE 2 3 ESC MENU WXYZ TUV PQRS GHI JKL MNO DEF ABC RESET SILENCE RESOUND M...

Page 17: ...e Typical Arrangement Active EOL Typical Sounder Arrangement OBSERVE POLARITY The Active EOL device is polarity sensitive The Active EOL is fuse protected however if connected incorrectly and the soun...

Page 18: ...C MENU WXYZ TUV RS HI JKL MNO DEF ABC BS EN 54 2 1998 BS EN 54 4 1998 BS EN 12094 1 2003 CLASS A EXTINGUISHANT RELEASE PULL DOWN AND PRESS BUTTON 6K8 6K8 470R VALVE FULLY OPEN NORMAL VALVE FULLY CLOSE...

Page 19: ...t the minimum voltage at the end of the circuit exceeds the minimum required by the solenoid typically 18V at the minimum actuator circuit output voltage The voltage at the end of the circuit is given...

Page 20: ...PROG Input 2 PROG Input 3 PROG Input 4 MANUAL ONLY AUTO MANUAL LOW PRESSURE MANUAL DISABLED DISABLED FAULT TIMER HELD ABORTED RELEASE IMMINENT RELEASED EXTINGUISHANT POWER SYSTEM FAULT TEST SOUNDER DE...

Page 21: ...GHI JKL MNO DEF ABC R E S ET S ILE N CE M U T E SILENCE SOUND ALARMS EXTINGUISHANT RELEASE PULL DOWN AND PRESS BUTTON PL3 PL4 SLIDE IN LABEL Using a sharp knife cut through the fascia label using the...

Page 22: ...y forward Ahr Total Load Quiescent Alarm Ahr x 1 25 16 Battery De rating factor Ahr 11 Figure quoted is for mains fail condition backlight off add 15mA for first hour of fault when the backlight is on...

Page 23: ...this number is lost it is not possible to enter commission mode functions Refer to 5 1 for further information 3 1 2 Front Panel Controls and Indications Key Switch Assembly Optional USB SUPPLY PSU C...

Page 24: ...select the Enable Controls option The display prompts for entry of the password Enter the password As each number is pressed an character is displayed Finally press the button to confirm Level 2 Menu...

Page 25: ...TECTION ZONE 1 ZONE 2 ZONE 3 Configuration of the Detection Zone Input Circuits 4 ALARM OUTPUTS SOUNDER 1 SOUNDER 2 SOUNDER 3 PULSE PATTERN Configuration of the Alarm Sounder Output Circuits and pulsi...

Page 26: ...ed parameter and then press the button to select change it The table below details the parameters can be adjusted Parameter Comments Description Options Default Setting SNDR DELAY Determines if the so...

Page 27: ...any pre existing state during the countdown period OFF PULSED ON ON ON PULSE2 STAGE 2 Determines the response of the output when the actuator output activated condition has been established OFF PULSED...

Page 28: ...1 Enter New Value 0 Maximum 7 The current on off period is shown Enter a new on off period as required Parameter Comments Description Options Default Setting PULSE 1 ON Specifies the Sounder ON period...

Page 29: ...signal 0 1800 Seconds 300 MINS TO RESET Specifies the minimum time that must elapse before a reset can be performed after the activated condition has been established 0 30 Minutes 10 HELD COUNTDOWN S...

Page 30: ...he activated condition is established when a fire occurs on Zone 1 X IMMEDIATE Z2 Determines if the activated condition is established when a fire occurs on Zone 2 X IMMEDIATE Z2 Determines if the act...

Page 31: ...Activating an input with this setting will select MANUAL ONLY mode Note When multiple inputs are defined as mode select then any switch in the active state will set the system into MANUAL ONLY mode HO...

Page 32: ...RELEASED The output is activated when the release of extinguishant has been completed AUX RELAY 8 ON HOLD The output is activated when the release of extinguishant has been held SWITCHED AUX ABORTED T...

Page 33: ...Stage 1 is active SWITCHED AUX STAGE 1 INVERTED NO 3 3 6 Passwords The display presents a menu of user password options Select User USER 1 1234 USER 1 1234 USER 2 1234 USER 3 1234 ENGINEER 7654 Use th...

Page 34: ...yy hh mm 06 01 2020 10 00 Mute Determines if the panel permits the buzzer to be muted at Level 1 or if it can only be muted at Level 2 LEVEL 1 LEVEL 2 LEVEL 1 Reset Mode Determines if the user is pres...

Page 35: ...ttings ACTIVE NO INPUT 1 NOT IN USE INPUT 2 NOT IN USE A list of the RSI programmable functions is presented Use the buttons to highlight the required RSI function and then press the button to select...

Page 36: ...current status of the link Possible status messages are LOGO UPDATE PC EVENT DATA TRANSFER PC CONFIG DATA TRANSGER PC NOTE When this function is enabled and in use any fault reporting of power supply...

Page 37: ...ll entries in the logbook have been addressed check the event log in the panel and take the necessary remedial actions b Visually inspect the panel for any moisture ingress or other deterioration chec...

Page 38: ...for further information Manufacturer Part Numbers YUASA POWERSONIC 4AH NP4 12 5AH PS 1250 F1 7AH NP7 12 7AH PS 1270 STOP For optimum performance and charge retention Yuasa recommend that batteries ar...

Page 39: ...vel 3 Programming Functions entering 1 when prompted for the password As soon as the Password Invalid message is shown press the 0 button and the display will show a decryption key Make a note of this...

Page 40: ...7 Series 65 Heat CS 32 26 Apollo ORB OP 12001 APO ORBIS Photo smoke 16 16 ORB OH 13001 APO ORBIS Multi sensor 16 16 ORB HT 11001 APO ORBIS A1R Heat 16 16 ORB HT 11002 APO ORBIS A2S Heat 16 16 ORB HT 1...

Page 41: ...rs 32 13 ST I using 330R base Sensortec Ion smoke 32 13 ST P using 330R base Sensortec Photo smoke 32 13 STA D5 using 330R base Sensortec Duct smoke 32 13 System Sensor ECO1002 standard base no resist...

Page 42: ...e TW950 Tyco Thermal Controls Mineral Insulated Twin Twisted PYRO E CCM2T Tyco Thermal Controls Pyrotenax Served Mineral Insulated Cable light and heavy duty Tyco Thermal Control Pyro S Wrexham Minera...

Page 43: ...u the Manual Only Mode will automatically be re instated I can t reset the control panel during the pre discharge countdown As default resetting the gas release during the countdown is prevented to co...

Page 44: ...www advancedco com 44 This page is intentionally left blank...

Page 45: ...www advancedco com 45 This page is intentionally left blank...

Page 46: ...www advancedco com 46 This page is intentionally left blank...

Page 47: ...www advancedco com 47 USER NOTES...

Page 48: ...ystem Emergency Abort Device Activation of Alarm Devices with Different Signals Response delay activated condition maximum 3s Response delay triggering of outputs maximum 1s EN54 2 1997 A1 Control and...

Reviews: