Advanced Air UK Ltd
Burrell Way
Thetford
Norfolk IP24 3QU
Tel: 01842 765657
Email: [email protected]
2530 CE Series
Smoke Fire Damper
Due to continuous product development Advanced
(U.K.) Ltd reserves the right to change any
information without prior notice
Date
Issue
Sheet
Spec Number
April 2018
C
27 of 34
TS2530CE-01
G:\PRODUCTS\DMP - 2500 Series\05 Product Data\2530\Tech Sub\2530CE\TS2530CE-01 Technical Sub Rev C.docx
Installation & Maintenance
Damper Testing and Conformity Details
To meet the requirements of the Construction Products Regulation 1
st
July 2013 Advanced Air fire/smoke dampers
meet the requirements of the product standard BS EN 15650 with a classification under BS EN 13501-3 as stated
in our declaration of performance that has been assessed by the notified certification body.
Installation type
Damper type
Test details
Classification
Blockwork wall
AFS
Motorised fire damper installed with AFS
frame single section and multi-section.
Min 100x100mm, Max 1000x1000mm
single section.
No stated maximum size if multi-section.
BRE 289678
BRE 289680
Efectis R000740
Efectis R000682
E120 (ve i↔o)S
Blockwork wall
HEVAC
Motorised fire damper installed with
HEVAC frame single section.
Min 100x100mm, Max 1000x1000mm
BRE 284807
BRE 287379
Efectis R0261A
Efectis R000740
E120 (ve i↔o)S
Drywall
AFS
Motorised fire damper installed with AFS
frame single section and multi-section.
Min 100x100mm, Max 1000x1000mm
single section.
No stated maximum size if multi-section.
BRE 284808
BRE 284809
Efectis R000740
Efectis R000682
E120 (ve i↔o)S
Concrete floor
AFS
Motorised fire damper installed with AFS
frame single section.
AFS rail is not
supplied by Advanced Air on floor
dampers.
Min 100x100mm, Max 1000x1000mm
Efectis R001256
Efectis R000740
E120 (ho i↔o)S
Concrete floor
HEVAC
Motorised fire damper installed with
HEVAC frame single section.
Min 100x100mm, Max 1000x1000mm
Efectis R0169B
Efectis R0169C
Efectis R000740
E120 (ho i↔o)S