![Advanced Air 2530 CE Series Manual Download Page 20](http://html1.mh-extra.com/html/advanced-air/2530-ce-series/2530-ce-series_manual_2855759020.webp)
Advanced Air UK Ltd
Burrell Way
Thetford
Norfolk IP24 3QU
Tel: 01842 765657
Email: [email protected]
2530 CE Series
Smoke Fire Damper
Due to continuous product development Advanced
(U.K.) Ltd reserves the right to change any
information without prior notice
Date
Issue
Sheet
Spec Number
April 2018
C
20 of 34
TS2530CE-01
G:\PRODUCTS\DMP - 2500 Series\05 Product Data\2530\Tech Sub\2530CE\TS2530CE-01 Technical Sub Rev C.docx
Storage - Important
The 2500 series damper is not a weatherproof product and it is important that dampers are stored in a
clean, dry environment at ambient temperatures. Temperatures in excess of 38°C may cause irreversible
damage to the molecular structure of the solder on actuator sensing element which can cause premature
activation of the damper.
The packaging that Advanced Air products are shipped in is not weather proof or fire resistant.
Approximate Weights – kg.
Width mm.
100
200
300
400
500
600
700
800
900
1000
H
e
ig
h
t
m
m
.
100
7
8
10
12
13
15
17
18
21
25
200
8
9
11
13
15
17
18
21
25
28
300
9
11
13
15
17
19
21
25
28
31
400
11
13
15
17
20
22
25
28
31
34
500
13
15
17
20
22
25
28
31
34
36
600
15
17
19
22
25
28
31
34
36
39
700
17
19
22
25
28
31
34
36
39
44
800
19
21
23
26
29
33
36
39
44
47
900
21
22
26
29
33
36
40
44
47
50
1000
22
25
28
32
36
39
43
47
50
54
IMPORTANT: Please add 10% to these figures for models with HEVAC frames.
Acoustic performance
Velocity
m/s
Damper blade position
OPEN
20 degrees
40 degrees
60 degrees
80 degrees
Pa
L
WA
Pa
L
WA
Pa
L
WA
Pa
L
WA
Pa
L
WA
0.5
< 5
< 30
< 5
< 30
< 5
< 30
22
44
255
67
1
< 5
< 30
< 5
< 30
8
38
85
59
1010
82
2
< 5
31
< 5
35
28
53
335
74
>2000
>90
4
< 5
46
10
50
110
68
1395
89
>2000
>90
6
< 5
55
22
59
250
77
> 2000
>90
>2000
>90
8
< 5
61
40
65
440
83
>2000
>90
>2000
>90
10
< 5
66
60
70
690
88
>2000
>90
>2000
>90
The above figures are approximate for use selecting multi-blade dampers