ADOS S.R.L. Buccinasco (MI)
417-MTA200I1
Rev. 9
Page 57 of 77
5.3
Operating parameter configuration
5.3.1 Operating parameter selection
Entering the configuration from the configuration level selection menu the instrument prepares to
configure the first parameter and displays the following message:
D i v i s i o
n
Press the
F
key to sequentially select all the configurable parameters (after reaching the last one it
returns automatically to the first one).
Pressing the numeric keys directly sets the number of the parameter to be configured.
Press the
N/G
key to decrease the number of the parameter selected (after reaching the last one it
returns automatically to the first one).
Press the
C
key to cancel the configuration request and return to the configuration level selection
menu.
Press the
E
key to confirm the selection made and the instrument prepares to configure the
parameter selected: the primary display indicates the value or the code of the parameter and the
auxiliary display flashes to indicate that the instrument is prepared to accept the change to the value
of the parameter.