instrument clears the “Batch in Progress” and “Batch in Alarm” status, de-activates the
relative outputs and goes to phase 0 (Batch de-activated).
3
This is the weight stabilisation phase and is used to recover the fly of the product.
If defined in configuration, the instrument activates a wait timer whose value can be
checked on the aux display:
STB 0008
When the time expires the dosed weight is checked:
⇒
if the weight is less than the [set minus fly] value, the “Slow” or “Fast” phase is re-
activated (it depends on whether or not the slowdown is present)
⇒
if the weight is in tolerance, the systems goes to phase 5 (end component control)
⇒
if the weight is out of tolerance, the system goes to phase 4 (component out of
tolerance control)
4
This is the out of tolerance control phase.
A blinking message “
ACK TOLL
” is displayed.
The “Batch in Alarm” output is activated and the status of the ACK and PAUSE/ABORT
input is checked:
⇒
if the operator closes the ACK input, the instrument de-activates the “Batch in Alarm”
output and goes to phase 7 (end component control)
⇒
if the operator closes the PAUSE/ABORT input, the instrument de-activates the
“Batch in Alarm” output and goes to phase 8 (end cycle control)
7
This is the End Component control phase.
The instrument performs the following operations:
⇒
prints the value of unloaded meterial
⇒
activates the wait timer between one component and the next one
⇒
when the wait timer expires places the system in the NET status and calculates the
TARE
Instrument goes to phase 0