![Adeunis RF COMFORT MQTT User Manual Download Page 62](http://html1.mh-extra.com/html/adeunis-rf/comfort-mqtt/comfort-mqtt_user-manual_3047350062.webp)
User Guide | COMFORT SERENITY MQTT | NB-IoT / LTE-Cat-M1
62
There are no alarms for humidity and VOC.
Configuration of Applicable Parameters to Use
Parameters
Unit
Value
Description
Transmission
Frequency
Seconds
0
No periodic
transmission of
T+H+CO2+VOC
values
Sensor Sampling
Frequency
Seconds
600
1 measurement
every 10 minutes for
T+H+CO2+VOC
CO2 Alarm Activation
-
Enabled
CO2 concentration
alarm activated
CO2 High Threshold
Detection
ppm
1300
High threshold to
trigger the alarm is
1300 ppm
Hysteresis
ppm
30
Hysteresis value is
30 ppm
Temperature Alarm
Activation
-
Enabled
Temperature alarm
activated
Temperature High
Threshold Detection
°C
25
High threshold to
trigger the alarm is
25°C
Temperature Low
Threshold Detection
°C
19
Low threshold to
trigger the alarm is
19°C
Hysteresis
°C
1
Hysteresis value is
1°C
Humidity Alarm
Activation
-
Disabled
Humidity alarm
disabled
VOC Alarm
Activation
-
Disabled
VOC alarm disabled