User Guide | COMFORT SERENITY MQTT | NB-IoT / LTE-Cat-M1
61
The table below lists the parameters to configure for using this transmission mode:
Parameters
Description
Default Configuration
Transmission Frequency
Frequency of data
transmission
3600 seconds
Sensor Sampling Frequency
Sampling frequency of
Tempe Hu
CO2 + VOC values
3600 seconds
High Threshold Detection
Threshold beyond which the
product will trigger a
transmission of the sensor
measurement
-
Low Threshold Detection
Threshold below which the
product will trigger a
transmission of the sensor
measurement
-
Hysteresis
Hysteresis value for high and
low thresholds
-
Threshold Status
Identifies an error in the
configuration of different
thresholds
-
These parameters can be configured via the NFC IoT Configurator app.
Example
The product measures temperature, humidity, CO2 concentration, and relative
change in volatile organic compounds every 10 minutes.
Alarms are configured for the product to notify the MQTT broker:
If the temperature exceeds 25°C. This alarm will be disabled if the temperature
falls below 24°C.
If the temperature goes below 19°C. This alarm will be disabled if the
temperature rises above 20°C.
If the CO2 concentration exceeds 1300 ppm. The CO2 alarm will be disabled if
the concentration falls below 1270 ppm.