72
Installation and Commissioning Guide 500-700 Tri-Capacity Split Ducted
Doc. No.0525-098
Ver. 2 210330
Installation and Commissioning Guide
Split Tri-Capacity
Airflow
(l/s)
External Static Pressure (Pa)
50
100
150
200
250
300
350
400
450
500
%
Spd.
W
%
Spd.
W
%
Spd.
W
%
Spd.
W
%
Spd.
W
%
Spd.
W
%
Spd.
W
%
Spd.
W
%
Spd.
W
%
Spd.
W
2500
48.2 869
51.5 1030 56.1 1269 59.9 1505 63.8 1765 67.9 2028 72.0 2297 75.8 2579 78.8 2875 83.2 3310
2600
49.2 905
53.3 1107
57.5 1350 61.3 1596 65.3 1864 69.5 2134 73.5 2398 76.8 2683 79.6 2973 84.6 3490
2700
50.2 941
55.1 1188 58.9 1435 62.8 1694 66.9 1965
71.1 2239 75.0 2495 77.8 2792 81.1 3096 88.1 3550
2800
52.2 1023 56.6 1275 60.3 1523 64.3 1792 68.6 2073 72.6 2346 76.1 2627 78.9 2913 83.2 3235
2900
54.1 1106 58.0 1357
61.9 1623 66.0 1900 70.4 2191
74.1 2468 77.2 2751 80.1 3032 85.5 3372
3000
55.9 1196 59.5 1446 63.5 1725 67.8 2013 71.9 2303 75.4 2580 78.5 2869 82.6 3198
3100
57.5 1284 61.2 1548 65.1 1830 69.7 2133 73.4 2406 76.9 2703 80.1 3001 84.8 3371
3200
59.1 1368
62.9 1652
67.1 1945 71.4 2238 75.0 2509 78.4 2854 82.4 3192
3300
60.9 1480 64.6 1764 69.2 2059 73.1 2355 76.6 2676 80.1 3044 84.8 3363
3400
62.7 1594 66.8 1887
71.1 2184 74.8 2486 78.3 2850 82.4 3188
3500
64.5 1708 68.9 2010 72.8 2315 76.4 2641 79.9 3009 85.0 3342
MOTOR / BLOWER LIMIT
3600
66.7 1837 70.9 2144 74.6 2452 78.1 2802 82.4 3155
3700
69.0 1975 72.8 2277 76.4 2603 79.9 2961 85.0 3315
3800
71.1 2107 74.8 2411 78.2 2769 82.5 3130
3900
73.1 2244 76.6 2578 80.0 2952 85.4 3292
INDOOR UNIT FAN CURVE
AIRFLOW (l/s)
Nominal Airflow = 3200 l/s
APPLICATION RANGE
EXTERNAL S
TA
TIC
PRE
SSURE (P
a)
Thermoregulat. Gfc4
Supply Fan
Minimum Temp.
5.0
o
C
Maximum Temp.
50.0
o
C
Minimum speed:
48.2%
Medium speed:
62.9%
Maximum speed:
90.0%
Supply Fan Temp.
Set Fan Speed
*
Service
Service Settings
Thermoregulation
Thermoregulat. Gfc4
NOTES:
% Speed
= Indoor Fan Speed Control Setting, in percent
(Value is set on the Control Interface via Service Menu
*
).
W
= Indoor Fan Power, Watts
- Data in the box indicates Factory Default Setting.
NOTE
Fan Performance Data and Fan Curve shown is at dry coil and with no air filters installed. Consider external static pressure drop specific to your design
requirements. Airflow should be reduce with respect to the moisture content in the air. Please review filter manufacturer for application. 2.5 m/s face
velocity point will occur at 4097 l/s.
CAY620T / EVY620T
FAN PERFORMANCE DATA
2500
3200
3100
3800
2800
3500
2600
3300
2900
3600
2700
3400
3000
3700
500
250
400
150
300
50
0
450
200
350
100
0
50
100
150
200
250
300
350
400
450
500
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
62.9% Speed
85% Sp
eed
80% Sp
eed
75% Sp
eed
70% Sp
eed
60% Sp
eed
55% Sp
eed
65% Sp
eed
3900
4000
4100
50% Sp
eed
90% Sp
eed
MOTOR / BLOWER LIMIT