Installation and Commissioning Guide
Split Tri-Capacity
51
Installation and Commissioning Guide 500-700 Tri-Capacity Split Ducted
Doc. No.0525-098
Ver. 2 210330
3. Divide the determined % Fan Speed by 10 to get the corresponding voltage to the nearest one decimal
figure.
Example:
Unit Model:
CAY620T / EVY620T
Airflow: 3200 l/s
External Static Press: 100 Pa
Required Fan Speed: 62.9%
LED FAN STATUS Display (Divide Required Fan Speed by 10): 6.2V ( 62.9 / 10);
LED adjustments are in 0.1V increments.
4. Use this calculated fan voltage to set the indoor speed via the CIB01 Fan Control.
5.
5. Set DIP switch 2 to
Set DIP switch 2 to
ON
ON
and using slotted screwdriver adjust CIB01 by rotating the Voltage Adjustment
and using slotted screwdriver adjust CIB01 by rotating the Voltage Adjustment
(Potentiometer) to obtain the desired voltage. Clockwise to increase the voltage and counter-clockwise to
(Potentiometer) to obtain the desired voltage. Clockwise to increase the voltage and counter-clockwise to
decrease the voltage.
decrease the voltage.
LED FAN STATUS Display will alternately show (Stand Alone) and (0-10V Out Speed Control).
(CIB01)
COMMERCIAL INDOOR BOARD
LED FAN
STATUS
DISPLAY
(
/
)
PWM1
A N
G N
A
A N
PWM2
A B
485 OUTDOOR
COM NC NO
AUX OUTPUT
10V 0V
0 - 10V OUT
10V 0V
0 - 10V IN
DIP
SWITCH
POT
ADJUST
UNIT SET
COM DN
FAULT INPUT
COIL TEMP
AUX SENSOR
VOLTAGE
ADJUSTMENT
(POTENTIOMETER)
SET TO
F
0 1
9
5
D
2
A
6
E
3
B
7
F
4
C
8
0 1
9
5
D
2
A
6
E
3
B
7
F
4
C
8
UNIT SET
SET DIP SWITCH 2
TO
ON
FOR STAND
ALONE OPERATION
1 2 3 4
ON
DIP
SWITCH
UNIT SET
1 2 3 4
ON
CIB01 SPEED RANGE AND UNIT SET DIAL POSITION *
(CIB01) COMMERCIAL INDOOR BOARD
ACTRONAIR PART NUMBER: 2020-134
Models
CIB01 Speed Range (v/%)
Minimum
Nominal
Maximum
STANDARD PROFILE
CAY500T / EVY500T
3.9/39.6
5.4/54.1
7.5/75
CAY620T / EVY620T
4.8/48.2
6.2/62.9
9.0/90
CAY700T / EVY700T
5.2/52.2
7.0/70.9
9.0/90
LOW PROFILE
CAY500T / ELY500T
4.0/40.7
5.3/53.2
7.9/79
CAY620T / ELY620T
5.4/54.7
7.0/70.1
8.9/89
CAY700T / ELY700T
6.0/60.2
7.7/77.2
8.9/89
*
Refer to specific model fan performance data and fan curve on the following pages for factory default fan settings.