90
Installation and Commissioning Guide 500-700 Tri-Capacity Split Ducted
Doc. No.0525-098
Ver. 2 210330
Installation and Commissioning Guide
Split Tri-Capacity
G. Service
e. Communicate config.
Ge1
Address:
Protocol:
MODBUS
CAREL
MODBUS EXT.
Speed:
19200
9600
4800
2400
1200
Ge2
Enable the BMS to turn the unit On / Off:
No
Yes
On loss of Comms:
Turn Off
Turn On
Use timeclock
Ge3
Enable DIN4 to turn the unit On / Off
No
Yes
G. Service
f. Service settings
a. Working hour set
Gfa1
Indoor Filter:
hours
Filter Fault relay:
Yes
No
Indoor Fan:
hours
Compressor:
hours
G. Service
f. Service settings
b. Probe Adjustment
Gfb1
(Return Air Temperature) Room Temp cal : °C
Gfc1
Room Temperature Setpoint:
o
C
Dead band:
o
C
Cool Proportion band:
o
C
Heat Proportion band:
o
C
Integral Time:
second
Gfc2
Room Temperature use INDOOR sensor
After Hours :
SW and Temp.
SW Only
Probe weight value :
Room Temp.:
o
C
Wall Cont Temp.:
o
C
Control Value:
o
C
Gfc4
Supply Fan
Minimum speed:
%
Medium speed:
%
Maximum speed:
%
Supply Fan Temp.
Minimum temp.:
o
C
Maximum temp.:
o
C
Gfc5
Supply Fan Gen. 3:
No
Yes
Supply Fan Continuous:
No
Yes
Cycle on de-ice:
No
Yes
One Speed Fan:
No
Yes
Speed Fan:
Low
Med
High
Supply Fan Run-on:
second
Heat Start Delay:
second
Gfc6
Setpoint Limit Min. by user:
o
C
Setpoint Limit Max. by user:
o
C
User Setpoint:
User Mode Sel:
Modelock timer:
second
Gfc7
Enable Night Mode by Scheduler:
No
Yes
Start Time:
Finish Time:
Max Cond fan Spd:
%
cct 2 max Spd:
%
Gfc8
Multi Input 1
No
Yes
SUPPLY AIR TEMP
Probe Type
ECONOMY ENABLE
NTC
NIGHT MODE ENABLE
0-5V
0-10V STAGE CONT
ON/OFF
0-10V IN FAN SPD
4-20mA
VIEW ONLY INPUT
0-20mA
CO
2
SENSOR
0-10V
PHASE FAIL RELAY
Multi Input 2
No
Yes
SUPPLY AIR TEMP
Probe Type
ECONOMY ENABLE
NTC
NIGHT MODE ENABLE
0-5V
0-10V STAGE CONT
ON/OFF
0-10V IN FAN SPD
4-20mA
VIEW ONLY INPUT
0-20mA
CO
2
SENSOR
0-10V
PHASE FAIL RELAY
G. Service
f. Service settings
c. Thermoregulation
SYSTEM CONFIGURATIONS (To access this menu, please enter the Service password: 7378).