Installation and Commissioning Guide 500-700 Tri-Capacity Split Ducted
Doc. No.0525-098
Ver. 2 210330
Installation and Commissioning Guide
Split Tri-Capacity
Final defined value for the fan (on the CIB01 seven segment
has to be written on the unit wiring diagram
FINAL
COMMISSIOINING FAN SET POINT VOLTAGE
as shown on
the side.
R
This drawing remains the intellectual property of Actron Engineering
Pty Ltd. Reproduction, modification and/or distribution are prohibited
without written consent.
Base
Model No:
Variation:
Description:
EVY620-700T-6Q2
STANDARD
INDOOR EVAPORATOR WIRING DIAGRAM WITH
CIB01 INDOOR FAN CONTROL BOARD & EC INDOOR FAN
Variation Code:
N
A
240V AC
POWER IN
COM
10V
10V
A(+)
COM
DI1
0V
0V
B(-)
NC
FAULT
INPUT
0-10V
IN
0-10V
OUT
485
OUTDOOR
AUX
OUTPUT
AUX
SENSOR
COIL
SENSOR
1
3
1
2
NO
PWM
2
PWM
1
1
1
4
4
FAN
PO
W
ER
1
240V
A
C
FAN
PO
W
ER
2
240V
A
C
AA
NN
OFF
ON
DIP SWITCH
1 2 3 4
AC250VAC/10A FUSE1
GLASS FUSE
250V AC 10 A
SLOW BLOW
SIZE 5 x 20mm
POT
ADJUST
IFB
OFF
ON
EXTERNAL COM CONTROL
PWM % SPD CONTROL
0-10V OUT SPD CONTROL
EXT. COM - 3RD PARTY
0-10V IN FAN CONTROL
EXT. COM - POT ADJUST
FAN CONTROL
485 MODBUS COM CONTROL
1 2 3 4
IFB STANDARD
DIP SWITCH
SETTINGS
IF-1
3 EC
L1
L2
L3
RSA
RSB
GND
COM
NC
I02
YELLOW
BLACK
WHITE
GREEN
WHI
TE
BLAC
K
FIELD WIRING BY INSTALLER -
CABLE MUST BE 2 CORE 7/0.30
SHIELDED TWISTED PAIR DATA CABLE
WITH SCREEN WIRE CONNECTED TO
J9FBUS1 "GND" TERMINAL ON OCB IN
OUTDOOR UNIT
GREEN
YELLOW
ACTIVE
RSB (-)
RSA (+)
NEUTRAL
EARTH
LINE 1
LINE 3
LINE 2
CONNECTION
BY INSTALLER
INDOOR FAN
POWER IN
DATA
CONTROL
POWER IN
TO
CONDENSER
UNIT
WHI
TE
BLACK
(SERVICE
USE ONLY)
DO NOT
REMOVE LOOP
DIP
SWITCH
No. 2
UNIT SET
DIAL
POSITION
INDOOR
FAN
DEFAULT
FAN SPEED
(@100pa)
OFF
F
FAN SPEED SET VIA
CP05 & CP10 CONTROLLERS
- FACTORY DEFAULT
FINAL COMMISSIONING
FAN SETPOINT VOLTAGE
Fan Speed:
Date:
.................... V or %
....../....../.....
Rev.
Description
Date
By
PCR
A
ORIGINAL
Revision
A
0515-8804
A5
Size:
Drawing No:
Drawn:
Date:
11-01-2021
JL
Approved:
RL
Date:
11-01-2021
NOTE
When unit is commissioned as a system (Indoor - Outdoor
operation) make sure that the final defined value entered on screen
GFc4
is the same as the Medium speed on CP05.
1 2 3 4
ON
DIP
SWITCH
UNIT SET
SWITCH OFF
DIP SWITCH 2
18.03. Compressor Configuration
External input modes can be set up as per table below
Component
External Input
Configuration
Compressor
Configuration
Procedure
Wiring Diagram
Compressors
24VAC
18.03.01
26.01 /26.03
0-10VDC
18.03.02
26.02 /26.04
To configure the External Input of Compressors control combination, perform the specific configuration procedure
for the Compressors, as detailed below:
Unit control mode is set to
EXTERNAL INPUT
via
Gfc11
screen.
G. Service
Gf. Service settings
Gfc. Thermoregulation
Gfc11. S. Configuration
EXTERNAL INPUT
S. Configuration Gfc11
Unit control mode :
EXTERNAL INPUT
Supply Fan Control :
Select Wall Control :
SINGLE CL01
On screen
C1
, set the
Mode
to
Auto change over
, so the Third Party Control will have full control of the compressor
operation.
By setting the mode to
Cool only
will restrict the compressor operation to
Cool only
.
By setting the mode to
Heat only
will restrict the compressor operation to
Heat only
.
Auto cycle will cycle the indoor fans on/off with the compressor.
AUTO CHANGE OVER/HEAT/COOL
Options
Heat / Cool C1
Mode: AUTO CHANGE OVER
Fan mode: Auto cycle