Symptoms
Possible Cause
Troubleshooting
1 Panel gets hot
- Wiring fault in 12VDC supply
- Change a new panel module and turn ON the unit again
abnormally
after the verification
2 The LCD no display
- Wiring fault in 12VDC supply
- Correct the wiring problem
(blank screen)
- No power supply
- Check the wiring and supply 12VDC to panel
- Voltage supply too low
- Check the power source
- Module defective
- Change a new panel module
3 - -' for all status
-Panel cannot/ not yet
- Ensure the selected unit exits in the network
(quite a long time)
received the information
- Ensure the wiring is correct
from chiller or FCU completely
- Ensure the wiring is not defective
-Ensure the wiring has been isolated from high power cable
- That particular unit address
- Select a coherent unit address on the panel (refer to
is not recognized by the panel
6.2.2)
- Module defective
- Change a new m odule
4 ON/ OFF, COOL or
- Software limitation
- Ensure it is pressed (hold 1s) in [Summary Pages]
HEAT button not
not in other menu.
function
- Module defective
- Change a new m odule
5 Cannot switch to
- Software limitation
- Ensure this mode is available in current "Model" of
HEATING mode
Chiller, please refer to 6.2.4
6 Cannot switch to
- Software limitation
- Ensure this mode is available in current "Model" of
BOILING mode
Chiller, please refer to 6.2.4
7 No "Manual Defrost"
- Software limitation
- Ensure current running m ode is HEATING
item
8 Cannot step inside
- Software limitation. Panel has
- Refer to sym ptoms 3
[Set Parameter]
not received all the inform ation
from chiller com pletely
9 7 Days Programmable - Software limitation. User
Control of Chiller:
Timer not function
did not activate the schedule
- Ensure the "Tim er" in [Timer Menu] is set ENABLE
Control of Chiller:
- Ensure the 'Timer" in [Operation Menu] is set ENABLE
10 No beeping sound
- Software limitation. User
- Ensure "Buzzer" in [Panel Option] is set ON
when new alarm
did not set ON to the alarm
occurred
buzzer
11 No screen saver after - Software limitation. User did
- Ensure "Screen Saver" in [Panel Option] I set ENABLE
timeout
not set ENABLE to the screen
saver
12 Time always reset to
- No backup battery
- Replace coin cell battery
12:00am, 1st Jan 2000 - Energy of the backup battery is
low
13 Panel stop operation. - Unstable power supply
- Power off the panel. Take out the backup battery as well.
Whole operation
- Energy of the backup battery is
Replace with a new 3V coil cell battery if necessary. Put
freezing (hang)
low
back the backup battery into the panel and power on again
7. PROBLEM AND TROUBLESHOOTING
36
Summary of Contents for A5ACV 100 CR
Page 43: ...INSTALLATION A5ACV 30 55 75CR 41 ...
Page 44: ...A5ACV 30CR A5ACV 55CR 75CR 42 ...
Page 78: ...10 WIRING DIAGRAMS PA R T NO 50 13 9 026086 MODEL A5ACV 30CR 76 ...
Page 79: ...77 MODEL A5ACV 55CR ...
Page 80: ...MODEL A5ACV 75CR PA R T NO 50 13 4 083602 78 ...
Page 81: ...MODEL A5ACV 100 135CR 79 ...