MODEL : A5ACV100 / 135CR - COOLING
64
WATER
AVAIL.
PUMP
PUMP
COOL
POWER COOL
POWER COOL
POWER COOL
POWER FLOW
HEAD INPUT INPUT
CAP.
INPUT
CAP.
INPUT
CAP.
INPUT
CAP.
INPUT
RATE
PRESS.
POWER
AMP
kW
kW
kW
kW
kW
kW
kW
kW
m
3
/hr
kPa
W
A
4
30.76
8.99
30.29
9.15
27.91
9.93
26.48
10.40
3.98
217.54
951
1.83
5
31.84
9.05
31.48
9.20
31.48
10.04
27.73
10.57
4.25
203.33
975
1.87
6
32.68
9.09
32.33
9.26
32.33
10.16
28.60
10.72
4.40
194.90
987
1.90
7
34.00
9.15
33.88
9.32
31.59
10.27
30.22
10.91
4.79
172.70
1013
1.95
8
34.36
9.18
34.01
9.38
34.01
10.40
30.33
11.03
4.83
170.46
1015
1.95
9
35.20
9.23
34.85
9.44
34.85
10.52
31.20
11.19
4.86
168.20
1017
1.95
10
35.80
9.27
35.34
9.50
33.06
10.64
31.69
11.33
4.90
165.93
1019
1.96
4
42.21
11.84
41.56
12.05
38.30
13.08
36.34
13.70
5.46
204.78
817
1.81
5
43.69
11.91
43.20
12.12
43.20
13.22
38.05
13.92
5.83
193.19
838
1.86
6
44.84
11.97
44.36
12.20
44.36
13.38
39.24
14.12
6.04
186.19
850
1.89
7
46.66
12.05
46.49
12.27
43.35
13.52
41.47
14.36
6.57
167.40
879
1.95
8
47.15
12.09
46.67
12.35
46.67
13.69
41.62
14.53
6.62
165.47
881
1.96
9
48.30
12.15
47.82
12.42
47.82
13.85
42.81
14.73
6.67
163.53
884
1.96
10
49.12
12.20
48.49
12.50
45.36
14.01
43.48
14.91
6.72
161.57
887
1.97
WATER
AVAIL.
PUMP
PUMP
COOL
POWER COOL
POWER COOL
POWER COOL
POWER FLOW
HEAD INPUT INPUT
CAP.
INPUT
CAP.
INPUT
CAP.
INPUT
CAP.
INPUT
RATE
PRESS.
POWER
AMP
kW
kW
kW
kW
kW
kW
kW
kW
m
3
/hr
kPa
W
A
4
25.53
10.72
24.58
11.03
23.16
11.50
20.78
12.28
3.98
217.54
951
1.83
5
26.79
10.92
25.85
11.27
24.72
11.73
22.10
12.67
4.25
203.33
975
1.87
6
27.66
11.10
26.73
11.47
25.61
11.98
23.00
12.97
4.40
194.90
987
1.90
7
29.31
11.33
28.39
11.76
27.84
12.00
24.74
13.46
4.79
172.70
1013
1.95
8
29.41
11.46
28.49
11.88
28.06
12.49
24.81
13.57
4.83
170.46
1015
1.95
9
30.29
11.63
29.37
12.08
28.28
12.74
25.72
13.87
4.86
168.20
1017
1.95
10
30.78
11.78
38.65
12.24
28.49
12.93
26.21
14.07
4.90
165.93
1019
1.96
4
35.03
14.11
33.73
14.52
31.77
15.14
28.51
16.17
5.46
204.78
817
1.81
5
36.76
14.38
35.47
14.84
33.91
15.45
30.32
16.69
5.83
193.19
838
1.86
6
37.96
14.61
36.68
15.11
35.14
15.78
31.56
17.08
6.04
186.19
850
1.89
7
40.21
14.92
38.96
15.48
38.20
15.80
33.94
17.72
6.57
167.40
879
1.95
8
40.36
15.08
39.10
15.64
38.50
16.44
34.05
17.87
6.62
165.47
881
1.96
9
41.56
15.32
40.30
15.91
38.80
16.77
35.29
18.26
6.67
163.53
884
1.96
10
42.23
15.52
53.03
16.12
39.10
17.02
35.96
18.53
6.72
161.57
887
1.97
WATER
AVAIL.
PUMP
PUMP
COOL
POWER COOL
POWER FLOW
HEAD INPUT INPUT
CAP.
INPUT
CAP.
INPUT
RATE
PRESS.
POWER
AMP
kW
kW
kW
kW
m
3
/hr
kPa
W
A
4
19.83
12.59
17.93
13.22
3.98
217.54
951
1.83
5
21.16
13.02
19.12
14.21
4.25
203.33
975
1.87
6
22.07
13.35
20.04
14.48
4.40
194.90
987
1.90
7
23.82
13.88
21.51
14.97
4.79
172.70
1013
1.95
8
23.89
13.99
21.89
15.02
4.83
170.46
1015
1.95
9
24.81
14.32
22.82
15.29
4.86
168.20
1017
1.95
10
25.30
14.53
23.47
15.45
4.90
165.93
1019
1.96
4
27.21
16.58
24.60
17.41
5.46
204.78
817
1.81
5
29.03
17.15
26.24
18.70
5.83
193.19
838
1.86
6
30.28
17.57
27.50
19.06
6.04
186.19
850
1.89
7
32.69
18.28
29.52
19.71
6.57
167.40
879
1.95
8
32.79
18.42
30.04
19.77
6.62
165.47
881
1.96
9
34.04
18.85
31.31
20.13
6.67
163.53
884
1.96
10
34.71
19.13
32.21
20.34
6.72
161.57
887
1.97
MODEL
LE
A
V
IN
G
W
A
TE
R
TE
M
P
(°
C
)
40
A5ACV100CR
A5ACV135CR
MODEL
LE
A
V
IN
G
W
A
TE
R
TE
M
P
(°
C
)
A5ACV100CR
A5ACV135CR
MODEL
L
E
A
V
ING WA
T
E
R T
E
M
P
(
°C)
A5ACV100CR
AMBIENT TEMPERATURE ON CONDENSOR (°C)
42
46
A5ACV135CR
AMBIENT TEMPERATURE ON CONDENSOR (°C)
19
20
25
28
AMBIENT TEMPERATURE ON CONDENSOR (°C)
30
32
35
Summary of Contents for A5ACV 100 CR
Page 43: ...INSTALLATION A5ACV 30 55 75CR 41 ...
Page 44: ...A5ACV 30CR A5ACV 55CR 75CR 42 ...
Page 78: ...10 WIRING DIAGRAMS PA R T NO 50 13 9 026086 MODEL A5ACV 30CR 76 ...
Page 79: ...77 MODEL A5ACV 55CR ...
Page 80: ...MODEL A5ACV 75CR PA R T NO 50 13 4 083602 78 ...
Page 81: ...MODEL A5ACV 100 135CR 79 ...