6.2.5 Changing Mode Set Temperature
There are 2 ways to change the mode set temperature for the Chiller.
i) [Operation Menu]
25
<ENTER>
<ENTER>
Summary Pages
Main Menu
Operation Menu
<ESC>
<ESC>
In
[Operation Menu]
, select “
Cool Temp” / “Heat
Temp”
and press
ENTER
start setting or
ESC
to exit
to
[Main Menu].
Change value via
UP
or
DOWN
button, and then press
ENTER
to confirm the change or
ESC
to cancel.
In
[Set Parameter],
select “
Regulator”
and press
ENTER
. Press
ESC
to exit to
[Main Menu]
.
Select
“R3”/ “R5”
and press
ENTER
to start setting
or
ESC
to exit to
[Set Parameter]
menu.
Change value via
UP
or
DOWN
button. The
boarderline is limited by
R5&R6
(cool),
R7&R8
(heat).
Press
ENTER
to confirm or
ESC
to cancel.
OPERATION MENU
Status
: ON
Mode
:
Cooling
Cool Temperature
: 12.0° C
Heat Temperature : 40.0° C
OPERATION MENU
Status
: ON
Mode
:
Cooling
Cool Temperature
:
12.0° C
Heat Temperature : 40.0° C
1. General
2. Regulator
3. Compressor
4. Defrost
5. Antifreeze
6. Inverter
7. Alarm and Contact
R1 Cool SP
: 12.0°C
R2 Cool Diff
: 3.0°C
R3 Heat SP
: 40.0°C
R4 Heat Diff
: 3.0°C
R5 Min Cool SP : -20°C
R6 Max Cool SP : 40°C
R7 Min Heat SP : -20°C
R1 Cool SP
:
12.0°C
R2 Cool Diff
: 3.0°C
R3 Heat SP
: 40.0°C
R4 Heat Diff
: 3.0°C
R5 Min Cool SP : -20°C
R6 Max Cool SP : 40°C
R7 Min Heat SP : -20°C
Summary of Contents for A5ACV 100 CR
Page 43: ...INSTALLATION A5ACV 30 55 75CR 41 ...
Page 44: ...A5ACV 30CR A5ACV 55CR 75CR 42 ...
Page 78: ...10 WIRING DIAGRAMS PA R T NO 50 13 9 026086 MODEL A5ACV 30CR 76 ...
Page 79: ...77 MODEL A5ACV 55CR ...
Page 80: ...MODEL A5ACV 75CR PA R T NO 50 13 4 083602 78 ...
Page 81: ...MODEL A5ACV 100 135CR 79 ...