52
CORRECTION FACTORS WITH GLYCOL USE
WATER
PRESSURE
FLOW
DROP
10
1.015
1.06
20
1.04
1.12
30
1.08
1.18
40
1.135
1.24
GLYCOL %
LWT/ deg C
10
20
30
40
-5
0.89
0.87
0.77
-3.9
0.9
0.876
0.781
-1.1
0.925
0.925
0.892
0.796
1.7
0.945
0.938
0.906
0.809
4.4
0.956
0.949
0.918
0.82
7.2
0.965
0.958
0.927
0.829
10
0.962
0.957
0.926
0.828
CAPACITY FACTOR
GLYCOL
Summary of Contents for A5ACV 100 CR
Page 43: ...INSTALLATION A5ACV 30 55 75CR 41 ...
Page 44: ...A5ACV 30CR A5ACV 55CR 75CR 42 ...
Page 78: ...10 WIRING DIAGRAMS PA R T NO 50 13 9 026086 MODEL A5ACV 30CR 76 ...
Page 79: ...77 MODEL A5ACV 55CR ...
Page 80: ...MODEL A5ACV 75CR PA R T NO 50 13 4 083602 78 ...
Page 81: ...MODEL A5ACV 100 135CR 79 ...