HE Series Central Chillers
Chapter 6: 56 of 83
When the alarm history log is full (50 alarms) the oldest alarm is lost when a new
alarm occurs.
There are three types of alarms:
• Warnings are informational only. They do not change the operation of
the chiller.
• Compressor critical faults prevent the compressors, and therefore the
circuit, from running.
• System critical alarms prevent the entire chiller from running.
Alarms remain active until the system is taken offline, the circuit is
disabled or the alarm has been reset. Each alarm is in one of three reset categories:
• Auto reset. The alarms in this category are automatically reset when the
alarm condition is no longer present.
• User reset. The alarms in this category require a user to reset them from
the display to be reset.
• Auto reset until time. The alarms in this category have 2 variables
(number of alarms (X) & time (Y) in seconds). The alarm will auto reset until it
occurs more than X times in Y seconds at which point it must be reset by a user.
Optionally, two variables can be sampled at the time of the alarm. The
samples are stored in the alarm history.
Summary of Contents for HE Series
Page 22: ...HE Series Central Chillers 882 03862 00 12 02 2021 22 Fork Lift...
Page 30: ...HE Series Central Chillers 882 03862 00 12 02 2021 30...
Page 31: ...HE Series Central Chillers 882 03862 00 12 02 2021 31...
Page 33: ...HE Series Central Chillers 882 03862 00 12 02 2021 33...
Page 57: ...HE Series Central Chillers Chapter 6 57 of 83...
Page 60: ...HE Series Central Chillers Chapter 7 60 of 83 Updating a C pCO s Program Using a USB Stick...
Page 61: ...HE Series Central Chillers Chapter 7 61 of 83 Saving or Restoring Settings to a USB Stick...
Page 62: ...HE Series Central Chillers Chapter 7 62 of 83 Updating an Exor HMI Program using a USB Stick...
Page 63: ...HE Series Central Chillers Chapter 7 63 of 83 Downloading Alarm History to a USB Stick...
Page 64: ...HE Series Central Chillers Chapter 7 64 of 83 Downloading Chiller Logs to a USB Stick...
Page 65: ...HE Series Central Chillers Chapter 7 65 of 83 Changing the Exor IP Address...
Page 75: ...HE Series Central Chillers Chapter 10 75 of 83 10 2 Piping Schematic for Remote Cooled Chiller...
Page 76: ...HE Series Central Chillers Chapter 10 76 of 83...