HE Series Central Chillers
Chapter 6: 54 of 83
• Retransmission of the Chiller Out Temperature
• Retransmission of the Tank Temperature
Digital In
• Aux Alarm* (
See Aux Alarm in Alarm Section
)
• Compressor A Verification
• Compressor B Verification
• Evaporator Fluid Differential Pressure Switch*
• Fluid Flow Switch
• High Discharge Pressure Switch
• Phase Monitor* (
See Phase Monitor in Alarm Section
)
• Pump Tank Confirm*
• Remote Start*
*
Optional
Digital Out
• Alarm Horn.
• Alarm Warning - Activates when an alarm warning is active.
• Compressor A Starter.
• Compressor B Starter.
• Condenser Fan Active.
• Cooling Active - The output activates when one or more compressors are active.
• Pump Tank Enable - The output activates when the system is online.
• System Online - The output activates when the system is online.
Pump Enable
This output will activate when the chiller is online.
Reduced Fluid Flow Detection
When this option is installed the reduced fluid flow warning alarm and sensor failure
alarm are enabled. The reduced fluid flow sensor is used to show the percent difference
from optimal fluid flow.
Remote Setpoint
When this option is installed and enabled (remote SP mode variable set to remote), the
chiller will be controlled to the setpoint sent to the PLC’s configurable analog input
instead of the setpoint entered via the display.
Remote Start
Summary of Contents for HE Series
Page 22: ...HE Series Central Chillers 882 03862 00 12 02 2021 22 Fork Lift...
Page 30: ...HE Series Central Chillers 882 03862 00 12 02 2021 30...
Page 31: ...HE Series Central Chillers 882 03862 00 12 02 2021 31...
Page 33: ...HE Series Central Chillers 882 03862 00 12 02 2021 33...
Page 57: ...HE Series Central Chillers Chapter 6 57 of 83...
Page 60: ...HE Series Central Chillers Chapter 7 60 of 83 Updating a C pCO s Program Using a USB Stick...
Page 61: ...HE Series Central Chillers Chapter 7 61 of 83 Saving or Restoring Settings to a USB Stick...
Page 62: ...HE Series Central Chillers Chapter 7 62 of 83 Updating an Exor HMI Program using a USB Stick...
Page 63: ...HE Series Central Chillers Chapter 7 63 of 83 Downloading Alarm History to a USB Stick...
Page 64: ...HE Series Central Chillers Chapter 7 64 of 83 Downloading Chiller Logs to a USB Stick...
Page 65: ...HE Series Central Chillers Chapter 7 65 of 83 Changing the Exor IP Address...
Page 75: ...HE Series Central Chillers Chapter 10 75 of 83 10 2 Piping Schematic for Remote Cooled Chiller...
Page 76: ...HE Series Central Chillers Chapter 10 76 of 83...