HE Series Central Chillers
•
882.03862.00
• 12/02/2021
28
4-12 Electrical Connections
Supply electricity of the voltage, phase, and cycle listed on the serial tag. Total running amps
are also found in the specification tables on pages in the Appendix.
Bring properly sized power leads and ground from a fused disconnect (installed by your
electrician) to the module. Use dual-element fuses in the disconnect switch, sized according
to local electrical regulations. Make sure all electrical connections are tight.
HE -FLA CHART
Model
Size
Type
Standard Incoming Voltage (FLA)
460 VAC 208VAC 230VAC
380V/60HZ 400V/50HZ 575VAC
HE20
20 TON
RC/WC
41.4
77.3
77.1
54.6
41.5
29.7
HE25
25 TON
RC/WC
53.1
117.8
117.6
61.8
50.3
45.6
HE30
30 TON
RC/WC
61.6
128.0
127.7
77.8
57.5
54.2
HE40
40 TON
RC/WC
70.4
165.3
165.1
80.7
70.6
57.1
HE50
50 TON
RC/WC
86.1
194.3
194.1
118.1
86.3
78.7
HE60
60 TON
RC/WC
123.7
249.0
248.8
157.0
123.9
112.0
4-13 Initial Set Up
Check the shipping papers against the serial tag to be sure chiller size, type and voltage is
correct for the process that will be controlled. Central chillers are built with a voltage specific
compressor and cannot be re-wired for an alternate voltage.
Check the transformer primary voltage connections to be sure they are configured for the
electrical power you are using. The voltage at the main power connection must read within
plus or minus ten percent (±10%) of the voltage listed on the serial tag. Electrical connections
must conform to all applicable codes.
Connect the main 3 phase incoming power to the unit making certain that line one (1) L1 is
connected to the A phase, line two (2) L2 is connected to the B phase, and line three (3) L3 is
connected to the C phase. Check for proper rotation direction of fan(s) and pump(s). The best
route for the main power wiring is from the floor up to the right side of the enclosure on the
top.
Check that all wire connections are secure and correct.
** Caution**
; FLA Information is based on maximum size amp draw for each electrical
item. Your actual FLA number should be equal or smaller than what is listed. FLA is Based on
maximum, compressor * 1.25, fans, Process Pump, Recirc Pump, Phase Monitor and XFMR.
Important!
Refer to your local electrical requirements for proper feeder conductor
and supply disconnecting sizing. For instance, in the United States refer
to National Electric Code (NEC) Article 430-24 through 430-26, Table
310.15(B)(2)(a)
Summary of Contents for HE Series
Page 22: ...HE Series Central Chillers 882 03862 00 12 02 2021 22 Fork Lift...
Page 30: ...HE Series Central Chillers 882 03862 00 12 02 2021 30...
Page 31: ...HE Series Central Chillers 882 03862 00 12 02 2021 31...
Page 33: ...HE Series Central Chillers 882 03862 00 12 02 2021 33...
Page 57: ...HE Series Central Chillers Chapter 6 57 of 83...
Page 60: ...HE Series Central Chillers Chapter 7 60 of 83 Updating a C pCO s Program Using a USB Stick...
Page 61: ...HE Series Central Chillers Chapter 7 61 of 83 Saving or Restoring Settings to a USB Stick...
Page 62: ...HE Series Central Chillers Chapter 7 62 of 83 Updating an Exor HMI Program using a USB Stick...
Page 63: ...HE Series Central Chillers Chapter 7 63 of 83 Downloading Alarm History to a USB Stick...
Page 64: ...HE Series Central Chillers Chapter 7 64 of 83 Downloading Chiller Logs to a USB Stick...
Page 65: ...HE Series Central Chillers Chapter 7 65 of 83 Changing the Exor IP Address...
Page 75: ...HE Series Central Chillers Chapter 10 75 of 83 10 2 Piping Schematic for Remote Cooled Chiller...
Page 76: ...HE Series Central Chillers Chapter 10 76 of 83...