![ACS HE Series Operation And Instruction Manual Download Page 27](http://html2.mh-extra.com/html/acs/he-series/he-series_operation-and-instruction-manual_3046891027.webp)
HE Series Central Chillers
•
882.03862.00
• 12/02/2021
27
The standard HE central chiller has an operating range of 50°F to 80°F (10°C to 27°C). Pure water
can be used when the desired tank temperature is 50°F (10°C) or greater. To operate below 50°F
(10°C) refer to the ethylene glycol and propylene glycol curves below. Add a pre-mixed solution of
industrial quality (not automotive), inhibited ethylene glycol or propylene glycol and water to provide
freeze protection to a temperature 20ºF (11ºC) below the normal chiller operating temperature set
point.
Glycol and/or water, with an inhibitor, should be used to protect the materials (copper, steel, stainless
steel, and bronze) in the system from corrosion. If you intend to use straight water, we strongly advise
a minimum tank temperature of 50ºF (10ºC) or contact the service department.
The following glycol products are available:
Part Number Description
216.00014.00
Ethylene glycol, 5 gallons (18.9 liters)
216.00014.01
Ethylene glycol, 55 gallons (208.2 liters)
216.00013.00
Propylene glycol, 5 gallons (18.9 liters)
216.00013.01
Propylene glycol, 55 gallons (208.2 liters)
Figure 3: Ethylene Glycol and Propylene Glycol Curves
Pe rce nt G lyc ol Cu rves for Free ze P ro tec tion
-60.0
-50.0
-40.0
-30.0
-20.0
-10.0
0.0
10.0
20.0
30.0
40.0
0.0
10.0
20.0
30.0
40.0
50.0
60.0
% Gl ycol by Vol um e
Eth ylene G lycol
P rop ylene Glycol
Example:
45°F set point minus 20°F = 25°F.
From Figure 28, 25°F equates to 10% by volume of glycol required.
Summary of Contents for HE Series
Page 22: ...HE Series Central Chillers 882 03862 00 12 02 2021 22 Fork Lift...
Page 30: ...HE Series Central Chillers 882 03862 00 12 02 2021 30...
Page 31: ...HE Series Central Chillers 882 03862 00 12 02 2021 31...
Page 33: ...HE Series Central Chillers 882 03862 00 12 02 2021 33...
Page 57: ...HE Series Central Chillers Chapter 6 57 of 83...
Page 60: ...HE Series Central Chillers Chapter 7 60 of 83 Updating a C pCO s Program Using a USB Stick...
Page 61: ...HE Series Central Chillers Chapter 7 61 of 83 Saving or Restoring Settings to a USB Stick...
Page 62: ...HE Series Central Chillers Chapter 7 62 of 83 Updating an Exor HMI Program using a USB Stick...
Page 63: ...HE Series Central Chillers Chapter 7 63 of 83 Downloading Alarm History to a USB Stick...
Page 64: ...HE Series Central Chillers Chapter 7 64 of 83 Downloading Chiller Logs to a USB Stick...
Page 65: ...HE Series Central Chillers Chapter 7 65 of 83 Changing the Exor IP Address...
Page 75: ...HE Series Central Chillers Chapter 10 75 of 83 10 2 Piping Schematic for Remote Cooled Chiller...
Page 76: ...HE Series Central Chillers Chapter 10 76 of 83...