Figure 2: Typical HE Water Cooled Condenser Connections
4-10 Checking Motor Direction
All of our central chillers have their motor rotations properly phased at the factory. If compressors,
pumps, or fans are running in reverse rotation, disconnect and lock out the power source and reverse
any two power leads into the chiller disconnect switch.
Caution!
Do not switch leads at the motors, motor starters, or contactors.
Three-Phase Compressors
Scroll compressors are directionally-dependent and compress in one rotational direction. Reversing
rotation direction results in an elevated sound level and a substantially-reduced current draw.
Caution! Do not allow the compressor to run backwards for any length of time. Doing so will
result in compressor damage.
4-11 Tank Temperature Considerations
Warning! Operating the tank temperature setpoint below 50°F (10°C) without the
proper amount of glycol for freeze protection could result in a damaged
evaporator. ACS Group does not warrant the freeze up of the evaporator
under any circumstances.
Condenser Water
Condenser Water In
Summary of Contents for HE Series
Page 22: ...HE Series Central Chillers 882 03862 00 12 02 2021 22 Fork Lift...
Page 30: ...HE Series Central Chillers 882 03862 00 12 02 2021 30...
Page 31: ...HE Series Central Chillers 882 03862 00 12 02 2021 31...
Page 33: ...HE Series Central Chillers 882 03862 00 12 02 2021 33...
Page 57: ...HE Series Central Chillers Chapter 6 57 of 83...
Page 60: ...HE Series Central Chillers Chapter 7 60 of 83 Updating a C pCO s Program Using a USB Stick...
Page 61: ...HE Series Central Chillers Chapter 7 61 of 83 Saving or Restoring Settings to a USB Stick...
Page 62: ...HE Series Central Chillers Chapter 7 62 of 83 Updating an Exor HMI Program using a USB Stick...
Page 63: ...HE Series Central Chillers Chapter 7 63 of 83 Downloading Alarm History to a USB Stick...
Page 64: ...HE Series Central Chillers Chapter 7 64 of 83 Downloading Chiller Logs to a USB Stick...
Page 65: ...HE Series Central Chillers Chapter 7 65 of 83 Changing the Exor IP Address...
Page 75: ...HE Series Central Chillers Chapter 10 75 of 83 10 2 Piping Schematic for Remote Cooled Chiller...
Page 76: ...HE Series Central Chillers Chapter 10 76 of 83...