ACS-CONTROL-SYSTEM GmbH
l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
51
7 .3 Output
7 .3 .1 Analogue output – current 0…20mA
Operating range I
Out
0…20,5mA, max. 22mA
Permitted load R
L
≤ (U
S
- 9V) / 22mA
Step response time T
90
≤ Pulse rate t
p
(t
d
= 0s)
Start-up time t
On
≤ 1s
7 .3 .2 Analogue output – current 4…20mA
Operating range I
Out
3,8…20,5mA, min. 3,6mA, max. 22mA
Permitted load R
L
≤ (U
S
- 9V) / 22mA
Step response time T
90
≤ Pulse rate t
p
(t
d
= 0s)
Start-up time t
On
≤ 1s
7 .3 .3 Analogue output – voltage 0…1
0
V
Operating range U
Out
0 ... 10,5 V, max. 11 V
Permitted load R
L
≥ U
Out
/ 3mA
Step response time T
90
≤ Pulse rate t
p
(t
d
= 0s / R
L
= 10kR)
Start-up time t
On
≤ 1s
7 .3 .4 Switch output PNP S1 / S2 / S3 / S4
Function
PNP switch to +L
Output voltage U
Out
U
Out
≥ U
S
– 2V
Output current I
L
0… ≤ 200mA, current limited, short circuit protected
Step response time T
90
≤ Pulse rate t
p
(t
d
= 0s)
Rise time T
90
< 30µs (R
L
< 3kR / I
Out
> 4,5mA)
Start-up time t
On
≤ 1s
Switch cycles
≥ 100.000.000
7 .4 Measuring accuracy
Reference conditions
EN/IEC 60770-1
Environmental temperature
15…25°C
Environmental air pressure
860..1060kPa
Air humidity
45...75% r.F.
Warm-up time
t
On
240s
Supply voltage U
S
24V
DC
±0,1V
Calibration position
Vertical
Process connection bottom
Ideal reflective surface
No interference reflections
within signal beam
Characteristic deviation
3)
≤ ±2mm or ±0,2% of set measuring range
14)
Influence of supply voltage
Output 0/4...20 mA
≤ ±0,001% FS
2)
/ V
Output 0…10 V
≤ ±0,006% FS
2)
/ V
Load influence
Output 0/4...20 mA
≤ ±0,01% FS
2)
/ 100R
Output 0…10 V
≤ ±0,05% FS
2)
/ 1mA
Temperature deviation
Mean T
k
4)
Zero
≤ ±0,006% FS
2)
/ K
2)
Referring to nominal measuring span resp. full scale (FS)
3)
Nonlin Hyst Reproducibility
4)
T
k
= Temperature coefficient
14)
whichever is greater
Summary of Contents for Sonicont USN4SP
Page 58: ......