I1 - Linearization > Level - display scaling e.g. 0,4..1,8 m = 0..2000 m

3

I2 - Linearization > Percent 0..100 % - Lin. Percent 0..100 %

I3 - No linearization
J - Signal output > e.g. 0..100 % = 4..20 mA resp. 0..20 mA resp. 0..10V

R – Signal output > Percent 0..100 % - Lin. Percent 0..100 %

K - Error signal evaluation
L1 - Switch / reset switch point S1

L2 - Switch / reset switch point S2

L3 - Switch / reset switch point S3

L4 - Switch / reset switch point S4

M1 - Error indication function S1

M2 - Error indication function S2

M3 - Error indication function S3

M4 - Error indication function S4

T – Impulse output S1 for quantity counter
N1 - Display scaling > Distance e.g. 0..100 % = 1,8..0,4 m

N2 - Display scaling > Fill level e.g. 0..100 % = 0,4..1,8 m

N3 - Display scaling > Percent 0..100 % = 0..100 %

N4 - Display scaling > scaled e.g. 0..100 % = 0..2000

N5 - Display scaling > Signal Output 0..100 % = 4..20 mA resp. 0..20 mA resp. 0..10 V

O - Display unit > at display scaling scaled e.g. m

3

P - Error indication display

S – Quantity counter > e.g. m

3

/h, l/min

Q1 - Display - Distance e.g. 1,8..0,4 m

Q2 - Display - Fill level e.g. 0,4..1,8 m

Q3 - Display - Percent 0..100 %

Q4 - Display - scaled e.g. 0..2000 m

3

Q5 - Display - Signal Output 4..20 mA resp. 0..20 mA resp. 0..10 V

Summary of Contents for Sonicont USN4SP

Page 1: ...protection class IP65 IP67 Wide environmental temperature range 20 C to 70 C High accuracy characteristic deviation 0 2 of measuring range Integrated evaluation electronic Graphic display keyboard 4x...

Page 2: ...us The actual technical manual includes instructions for installation electrical connection and inauguration as well as the technical data of the device Modifications that answer the purpose of the te...

Page 3: ...ration and display parts 14 5 2 Function scheme 14 5 3 Menu structure 16 5 4 Navigation 17 5 5 Output 18 5 6 Basic setting 25 5 7 Display 31 5 8 Simulation E 37 5 9 Diagnosis 38 5 10 Data 41 5 11 Star...

Page 4: ...device is suitable for demanding measuring requirements Due to its high accuracy and the high flexibility of configuration the device can be suited a wide variety of applications The robust design an...

Page 5: ...asuring value is converted into a continuous current signal 0 4 20mA or voltage signal 0 10V The measuring value is diagrammed at the high brightness and high contrast TFT LCD display whereby it can b...

Page 6: ...al manual and the relevant standards and rules This expert must have read and understood this technical manual and especially the safety notes The device may only be used within the permitted operatio...

Page 7: ...ams are causing measurement errors the sensor should be used in a standpipe If there are strong air currents in the vessel e g due to strong winds in outdoor installations or air turbulence e g by cyc...

Page 8: ...hat the pipe is not soiled by accumulated dirt If necessary clean the pipe at regular intervals The pipe must be provided with a sufficient venting hole A 5 10mm at the upper edge 3 1 3Flow measuremen...

Page 9: ...ing result particularly if the level is very low 0 2bar resp 20kPa 3 2 2Vapor pressure The vapor pressure at 20 C 68 F gives a hint on the accuracy of the ultrasonic level measurement If the vapor pre...

Page 10: ...ideally 45 Note the specified limits for nozzle diameter and length Nozzle diameter D Maximum nozzle length L DN50 2 80mm DN80 3 240mm DN100 4 300mm DN150 6 400mm 3 2 6Standpipe measurement By using a...

Page 11: ...llation place of the device 4 3 Supply voltage The voltage applied to the terminal contacts may not exceed the maximum permitted supply voltage to avoid damage of the electronic The maximum permitted...

Page 12: ...ge Dependent on the connected supply voltage and the maximum output current it results in a maximum value for this resistor where a correct function is still possible 4 6 Connection scheme Conductor c...

Page 13: ...ACS CONTROL SYSTEMGmbHlLauterbachstr 57lD 84307Eggenfeldenlwww acs controlsystem delinfo acs controlsystem de 13 4 6 3Electronic output type R 1x signal 0 4 20mA 0 10V 4x switch PNP supply 24VDC...

Page 14: ...with the key up for a step backwards one menu item C Key Enter Shift right Access to operation menu In the selection menu entering the selected sub menu In the set menu applying the new value and dig...

Page 15: ...ror indication function S1 M2 Error indication function S2 M3 Error indication function S3 M4 Error indication function S4 T Impulse output S1 for quantity counter N1 Display scaling Distance e g 0 10...

Page 16: ...nu item menu structure Submenu output Settings for the function of the switch outputs and the signal output Submenu basic setting Settings for the basic adaption of the device to the measuring task e...

Page 17: ...t applying the changings is done by the simultaneous pushing the keys Up and Down The input of a value or text in a set menu is done digit by digit For the changing of the selected digit the keys Up a...

Page 18: ...sition in the extended menu structure This extended menu structure can be shown in the submenu display by the menu item menu structure A Hysteresis function B Window function C Error indication functi...

Page 19: ...wo position control The switch range is determined by definition of switch point and reset switch point In the menu Operating Mode the working principle of the switch output can be inverted Operating...

Page 20: ...point and the reset switch point and if the set reset switch point delay time has been expired The hysteresis is positioned outside the area that is defined by the switch point and the reset switch p...

Page 21: ...nd the reliability increased All switch outputs with activated pump control are not assigned to a certain switching point but are switched on or of depending on the accumulated operating time The sign...

Page 22: ...e switch output with the next higher index After the switch output with the highest index it will be changed to the switch output with the lowest index e g S1 S2 S3 S4 S1 S2 The order is valid for all...

Page 23: ...ch delay time will be considered that means the forced switchover to another pump is processed exactly after the time The set switch delay time for this pump must be expired before the new selected pu...

Page 24: ...values will be kept 0V At exceedance the error signal 0V is generated 11V At exceedance the error signal 11V is generated Default Off 5 5 2 3 Invert Signal Inverts dependent on the operating mode the...

Page 25: ...o Object detection Each measuring value at the set pulse rate will be displayed resp output o Fluid The measured signal will be checked for plausibility and fast signal changes 1m min e g due to an ag...

Page 26: ...range limits 2 points are defined that set the ratio of the measured distance signal and the operating range of the device The current measuring value is indicated in the display The input of the meas...

Page 27: ...high distance or a strong deviation of the ultrasonic signal up to the next valid measuring signal alternatively the last detected measuring value can be hold or the minimum resp maximum adjusted lim...

Page 28: ...ical vessels or also for flow calculation A Tank with linearization points 1 2 3 4 B Characteristic distance level not linearized C Characteristic distance level linearized 5 6 8 1 Predefined lineariz...

Page 29: ...ion At the input mode percent linearized percent the input signal refers percentual to the measuring range that is defined at the min max adjustment for 0 and 100 The output signal must also be consid...

Page 30: ...ee chapter Technical data supply voltage fail whereas a longer failure resets the values The values must then be set again At the battery powered system the values are buffered also at a long term fai...

Page 31: ...tructure This extended menu structure can be shown in the submenu display by the menu item menu structure 5 7 1Indicator value The measuring value can be alternatively displayed as distance as filling...

Page 32: ...7 3Unit This menu item is only available at indicator value scaled If a scaled indicator value is used additionally an unit can be selected that is indicated in the display not at indicator type verti...

Page 33: ...n different types Digital Switch points active or deactive Sensor TAG Digital measuring value Unit Quantity counter value only at activated function quantity counter Horizontal scaled bargraph Mark of...

Page 34: ...The measuring value cursor can be set to the oldest resp youngest measuring value or to an arbitrary point of time in days hours minutes seconds Navigation of the measuring value cursor with cursor ke...

Page 35: ...Up to 10 characters can be input The input range is indefinite Default no Password allocated 5 7 9Menu Structure For a breakdown illustration of the menu navigation different menu items mark E in the...

Page 36: ...tness of the backlight an automatic dim after 5 minutes of inactivity no key touch can be activated 0 10 20 30 40 50 Off Default Off 5 7 12 View E For the adaption of the display to the requirements o...

Page 37: ...h output is activated resp deactivated regardless of an already existing activation and also regardless of delay times 5 8 1 2 Signal Output At the signal output an analogue signal is output regardles...

Page 38: ...ce value is displayed with unit m and the corresponding measured signal level in dB Cursor resp Zoom mode Below and left of the characteristic curve the position of a shiftable cursor is indicated A s...

Page 39: ...frequency of occurrence Echo lost No measurable echo signal available Over Range exceeding the signal output range dependent on Operating Mode o 20 5 mA 4 20 mA o 20 5 mA 0 20 mA o 10 5 V 0 10 V Under...

Page 40: ...be separately reset by pushing the key Shift right Enter 5 9 6Operating Hours The operating hours of the device since the last device start up are detected The indication is done in hours 5 9 7Operat...

Page 41: ...an be displayed graphically in the indicator type chart or exported as CSV file per Bluetooth interface By the Bluetooth interface the download of linearization or firmware files is possible 5 10 1 Bl...

Page 42: ...After the selection end devices with Bluetooth ability are searched and after selection and approval the measuring values are transmitted 5 10 1 2 Receive CSV Lin Table To simplify enormous lineariza...

Page 43: ...es the time interval between two measuring values which should be stored in the measuring value memory The input range is limited to values from 1 to 99999 Default 60 s 5 10 4 Activation Recording To...

Page 44: ...the menu is displayed This value can be actualized by the keys Up or Down Unit Volume l hl m3 in3 gal ft3 User defined Up to 10 characters can be input The input range is indefinite Default no text al...

Page 45: ...surface to the sensor Sub menu Basic Setting Commissioning Min Max Adjustment Sub menu Display Indicator value fill level 5 11 1 1 Example Measurement task Distance Sensor container bottom 1 8m Minimu...

Page 46: ...splay Indicator value Scaled Unit Scaling ration percent tank volume 5 11 2 1 Example Measurement task Distance Sensor container bottom 1 8m Container Cylinder linear volume Minimum filling level 0 2m...

Page 47: ...vailable Sub menu Basic Setting Commissioning Min Max Adjustment Linearization Sub menu Display Indicator value Scaled Unit Scaling ration percent flow amount 5 11 3 1 Example Measuring task Style Tri...

Page 48: ...ACS CONTROL SYSTEMGmbHlLauterbachstr 57lD 84307Eggenfeldenlwww acs controlsystem delinfo acs controlsystem de 48 5 12Software history Version Date Modifications 4 1 0 07 2017 Original version...

Page 49: ...for repair the following information s must be enclosed An exact description of the application The chemical and physical characteristics of the product A short description of the occurred error 6 4...

Page 50: ...S1 S2 S3 S4 0mA Bluetooth Off 60 mA US 30 V UO S1 S2 S3 S4 0mA Bluetooth On 7 2 Input 7 2 1Measuring range type 02 2m Measuring range 2m Blocking distance BD 0 15m typ 0 06m Operating frequency 125kH...

Page 51: ...urrent IL 0 200mA current limited short circuit protected Step response time T90 Pulse rate tp td 0s Rise time T90 30 s RL 3kR IOut 4 5mA Start up time tOn 1s Switch cycles 100 000 000 7 4 Measuring a...

Page 52: ...Backlight LCD 60 20 C 60 C Backlight LCD 80 20 C 50 C Protection IP65 IP67 EN IEC 60529 Climatic classification 4K4H EN IEC 60721 3 4 Shock classification 15g 11ms EN IEC 60068 2 27 Vibration classif...

Page 53: ...GmbHlLauterbachstr 57lD 84307Eggenfeldenlwww acs controlsystem delinfo acs controlsystem de 53 8 Dimension drawings 8 1 Terminal enclosure 8 2 Process connection Type 5 Thread ISO 228 1 G1 B Measuring...

Page 54: ...ACS CONTROL SYSTEMGmbHlLauterbachstr 57lD 84307Eggenfeldenlwww acs controlsystem delinfo acs controlsystem de 54 Type 7 Thread ISO 228 1 G1 B Measuring range type 05 5m...

Page 55: ...ACS CONTROL SYSTEMGmbHlLauterbachstr 57lD 84307Eggenfeldenlwww acs controlsystem delinfo acs controlsystem de 55 Type D Thread ISO 228 1 G2 B Measuring range type 08 8m...

Page 56: ...process wetted 3 EPDM ethylene propylene dienmonomere Material process connection process wetted V CrNi steel Material terminal enclosure C CrNi steel Measuring range 02 2 m 05 5 m 08 8 m YY Special m...

Page 57: ...very of the device and must be ordered separately 9 3 1Installation material A wide range of accessories for device installation is constantly available e g Welding sockets Welding flanges Blind flang...

Page 58: ......

Reviews: