5 .11 .3
Flow measurement
For the indication of the flow amount a display scaling can be made.
If a nonlinear flow opening style is used, a linearization must be set.
Predefined linearization curves for some flow opening styles are available.
Sub menu Basic Setting
•
Commissioning
•
Min/Max Adjustment
•
Linearization
Sub menu Display
•
Indicator value Scaled
•
Unit
•
Scaling - ration percent / flow amount
5 .11 .3 .1
Example
Measuring task
•
Style: Triangle weir
•
Level minimum flow: 0,95m at 0 l/s
•
Level maximum flow: 0,45m at 69 l/s
Settings
•
Process commissioning
•
Min/Max Adjustment: 0,95m = 0% / 0,45m = 100%
•
Display Indicator value: Scaled
•
Display Unit: l/s
•
Display Scaling: 0% = 0 l/s / 100% =69l/s
•
Linearization: triangular weir
A - Distance at minimum flow
B - Distance at minimum flow
C - Maximum water level H
max