Operating Mode outside
The switch output is activated, if the current measuring value is outside the area that is defined by
the switch point and the reset switch point and if the set switch point delay time has been expired.
The switch output is deactivated, if the current measuring value is inside the area that is defined
by the switch point and the reset switch point and if the set reset switch point delay time has been
expired.
The hysteresis is positioned inside the area that is defined by the switch point and the reset switch
point.
•
Operating Mode inside
The switch output is activated, if the current measuring value is inside the area that is defined by
the switch point and the reset switch point and if the set switch point delay time has been expired.
The switch output is deactivated, if the current measuring value is outside the area that is defined
by the switch point and the reset switch point and if the set reset switch point delay time has been
expired.
The hysteresis is positioned outside the area that is defined by the switch point and the reset
switch point.
5 .5 .1 .4 .3 Error Indication Function S1/S2/S3/S4
The switch output is activated, if the device has detected a failure behavior (see chapter diagnose/
failures).
In the menu Operating Mode, the working principle of the switch output can be inverted.
5 .5 .1 .4 .4 Impulse Function S1
The switch output generates one switch impulse per calculated quantity value of the quantity
counter (see data/quantity counter).
A warning message is generated, if the quantity counter impulse value is set too low or the
impulse length is set too high. The calculation base for this warning message is the display scaling
at 100%.
•
Quantity counter impulse value
Amount of the quantity counter value, for which one switch impulse is generated.
The input range is indefinite.
Default > 1
•
Impulse length
Duration of a pulse resp. additionally the duration of a pulse pause.
The input range is limited to values from 0,1 to 99999.
Default > 0,5 s
In the menu Operating Mode, the working principle of the switch output can be inverted.