Operating mode 0-20mA
The linear output range is 0…20,5mA.
•
Off
>> At exceedance the limit values will be kept.
•
0mA >> At exceedance the error signal 0mA is generated.
•
22mA
>> At exceedance the error signal 22mA is generated.
Operating mode 0-10V
The linear output range is 0…10,5V.
•
Off
>> At exceedance the limit values will be kept.
•
0V
>> At exceedance the error signal 0V is generated.
•
11V
>> At exceedance the error signal 11V is generated.
Default > Off
5 .5 .2 .3 Invert Signal
Inverts, dependent on the operating mode, the analogue output signal.
•
4-20 mA >> 20-4 mA
•
0-20 mA >> 20-0 mA
•
0-10 V >> 10-0 V
Default > No
5 .5 .2 .4 Source
Defines the source for the generation of the signal output. For the source, it can be chosen between
the measuring value before (%) or after (Lin %) an optionally set linearization.
This allows e.g. the output of a linear filling level at the signal output, whereas a linearized volume is
shown at the display.
•
Lin %
•
%
Default > Lin %