background image

       BusWorks

  

Model 903MB/902MB/901MB Network I/O Module User’s Manual                                         Digital I/O 

       ___________________________________________________________________________________________ 

- 17 - 

Creating A Configuration File 

 
You may use 

File-New

 to create a new 

configuration file, or 

File-Open

 to open 

an existing configuration file.  You may 
also use 

Module-Upload 

Configuration

 to retrieve the current 

active configuration from the module 
connected (recommended).   

 
Uploading first is recommended as it will 
automatically detect the correct model 
connected and load the property sheets 
for that model. 

 
Once you create, open, or upload a 
configuration file, a screen similar to the 
one shown at right will be displayed.  
The model number is indicated at the 
top of the screen along with the current 
file name.  Model 903MB Configuration 
is shown here.  Your screen will vary 
according to your model number. 
 
Note that only 2 property sheets define 
this transmitter’s configuration: General 
and Test. 

                                                                                                                            

 

                                                                                                                    Module Present 
 

Module 

 
The Serial and Firmware numbers are 
indicated at the top of the General screen 
and cannot be modified. 

 
For “Tag:”, enter up to 15 alphanumeric 
characters (optional). 

 
For “Comment:”, enter up to 31 
alphanumeric characters (optional). 

 
For “Configured By:”, enter your name up 
to 15 alphanumeric characters (optional). 

 
You can also add a “Location:” note of up 
to 25 alphanumeric characters (optional). 
 
For “ID Port:”, enter up to 15 alphanumeric 
characters of identification information 
relative to the port (optional). 
 
Use the 

“Slave Address”

 scroll bar to 

select a new module address that will take 
effect following download.  Select from 1 to 
247.  Address 247 is reserved for Default 
Mode. 

 
Use the 

“Baud Rate”

 scroll bar to select a 

new baud rate to be used by the module 
following download.  Select 2400, 4800, 
9600 (Default Mode), 14400, 19200, 
28800, 38400, 57600, 76800, or 115200 
bits per second. 

 
Use the 

“Parity”

 scroll bar to select Odd, 

Even, or No Parity (Default Mode) error 
checking by the module. 

 
Use the 

“Response Delay”

 field to specify 

a delay from 0 to 65500 ticks with 1 tick 
equal to 1.085 micro-seconds.  Response 
delay is the additional turnaround delay 
applied between message receipt by the 
module and its response to the host.  A 
fixed amount of delay is already present 
and varies with the model.  Thus, you will 
have to specify a comparable amount of 
response delay to measure any affect.  
Some host software or signal converters 
require additional delay to work properly. 
 
Note that slave address, baud rate, parity, 
and response delay selections take effect 
following the next module reset and do not 
alter the settings used by the host software 
(which are configured separately via the 

Settings

 menu). 

 
If you checked the “Update 
Communications settings at download” box 
of the Settings pull-down menu, the host 
software will automatically change its own 
settings to match the module settings that 
take effect following download in an effort 
to easily maintain communication with the 
module.  Otherwise, you must change the 
host settings separately after downloading 
to match the new module settings. 

 
If the module is in Default Mode (indicated 
via a flashing status LED), the baud rate, 
address, and parity of the module are fixed 
at 9600bps, 247, and No Parity. 

 
The Test Screen of the next page also 
provides configuration information with 
respect to the port watchdog timers and 
output timeout states. 

Summary of Contents for 901MB

Page 1: ...t With Sinking Outputs And Active Low Inputs USER S MANUAL ACROMAG INCORPORATED 30765 South Wixom Road P O BOX 437 Wixom MI 48393 7037 U S A Tel 248 295 0880 Fax 248 624 9234 Copyright 2000 Acromag In...

Page 2: ...ning any type of control or monitoring system This is especially important where economic property loss or human life is involved It is important that the user employ satisfactory overall system desig...

Page 3: ...m with open drain outputs for convenient loopback monitoring of the output state High Speed Data Rates Supports half duplex RS485 baud rates up to 115K baud Key 903MB Module Features continued Conveni...

Page 4: ...LE INSTALLATION This transmitter module is packaged in a general purpose plastic enclosure Use an auxiliary enclosure to protect the unit in unfavorable environments or vulnerable locations or to main...

Page 5: ...ck wire insulation 1 4 inch on each lead before installing into the terminal block Since common mode voltages can exist on signal wiring adequate wire insulation should be used and proper wiring pract...

Page 6: ...s not require advanced familiarity with the Modbus protocol REGISTER MAP Modbus registers are organized into the following reference types identified by the leading number of the reference address Ref...

Page 7: ...bps Default 3 14400bps 4 19200bps 5 28800bps 6 38400bps 7 57600bps 8 76800bps 9 115200bps 40003 2 0002 Parity Default 0 None 0 None 1 or 2 stop bits 1 Odd Parity Checking 2 Even Parity Checking Model...

Page 8: ...mapping mirroring to the Holding Register space The format of the registers are identical and you only need to offset your address by 43000 For example if you want to read Input Register 1 through the...

Page 9: ...itional stop bit is normally transmitted to fill out the character frame for no parity Acromag units will accept one or two stop bits with no parity Modbus Addresses The master device addresses a spec...

Page 10: ...s Example Response Field Name Example Value Hex Slave Address 247 F7 Function Code 1 01 Byte Count 2 02 Data Coils 7 0 170 AA Data Coils 11 08 10 0A Error Check LRC or CRC To summarize the status of c...

Page 11: ...mmarize the contents of register 40001 two bytes is slave address 247 00F7H The contents of register 40002 two bytes is the baud rate setting 2 9600bps The contents of register 40003 is the parity set...

Page 12: ...t No response is returned to broadcast queries from a master device Force Multiple Coils 15 902MB 903MB Models Only This command will simultaneously force a sequence of coils 0x reference addresses ei...

Page 13: ...ta High Third Reg 0 00 Preset Data Low Third Reg 2 02 Error Check LRC or CRC Preset Multiple Registers Example Response Field Name Example Value Hex Slave Address 247 F7 Function Code 16 10 Starting R...

Page 14: ...6 bit signed integer value representing an A D count a DAC count or a time value with a range of 32768 to 32767 Percentage A 16 bit signed integer value with resolution of 0 005 lsb 20000 is used to r...

Page 15: ...nt a timeout error from occurring in the master 06 Slave Device Busy The slave is engaged in processing a long duration program command The master should retransmit the message later when the slave is...

Page 16: ...tly loaded configuration file Use File Print Preview to view the current configuration or preview the print documentation Use File Print Setup to select a printer and font style Module Upload Configur...

Page 17: ...g download Select from 1 to 247 Address 247 is reserved for Default Mode Use the Baud Rate scroll bar to select a new baud rate to be used by the module following download Select 2400 4800 9600 Defaul...

Page 18: ...k monitoring of the output state The source leads of each port output channel are tied in common to the port return lead RTN The drain leads are pulled up to the port excitation terminal via resistor...

Page 19: ...f each module Please refer to Acromag s Service Policy Bulletin or contact Acromag for complete details on how to obtain service parts and repair PRELIMINARY SERVICE PROCEDURE Before beginning repair...

Page 20: ...only Observe proper polarity Inputs include transient suppression devices and series connected 100K resistors plus diode over voltage clamps to the internal 5V supply Sockets are provided for installa...

Page 21: ...vision 2 Groups A B C D Consult Factory ENVIRONMENTAL SPECIFICATIONS Operating Temperature 25 C to 70 C 13 F to 158 F Storage Temperature 40 C to 85 C 40 F to 185 F Relative Humidity 5 to 95 non conde...

Page 22: ...ect outside of Default Mode until a software or power on reset has occurred Watchdog Timer A hardware watchdog timer is built into the microcontroller that causes it to initiate a self reset if the co...

Page 23: ...cation flag bits 2 0 of the Module Status register will be set if any of the port output channels have not been written to over the specified time period or if any of the port input channels have not...

Page 24: ...EXC1 100K SIP RES SOCKET INPUT BUFFER CONTROLS MULTIPLEXER 5V 5V 5V MICRO 100K 100K 5V STATUS LED 100K 100K 100K 100K INTEGRATED OUTPUT CONTROLS 5V PWR LED DEFAULT MODE SWITCH PUSH FOR DEFAULT MODE U...

Page 25: ...5 CH 3 42 CH 8 TB2 TB2 21 EXC2 23 CH 5 34 D 24 26 RTN 31 COM TB4 PWR D B A TB3 TB4 PWR D TB3 RS232 PORT COM 11 12 CJC 0 45 RTN OUT3 TB1 15 IN1 TB2 42 OUT1 TB3 COM TB2 23 26 25 IN2 IN3 IN3 INPUTS 2 3 3...

Page 26: ...FLASHES IN DEFAULT MODE PUSH FOR DEFAULT MODE DFT 9 8 7 6 ON WHEN OUTPUT CONDUCTING OR WHEN INPUT LOW DIGITAL CHANNELS STATUS LED YELLOW RUN PWR LED GREEN TB4 ST RUN Acromag DEFAULT MODE SWITCH SHIELD...

Page 27: ...OUTPUT IS OFF 0 FOR INPUT ONLY UNITS MODEL 901MB 0900 902MB 0900 903MB 0900 PAGE 3 OF 4 ELECTRICAL CONNECTIONS LED V 902MB 903MB OFF ON TO OTHER 3 CHAN OF PORT 100K I O RTN SOLID STATE RELAY SSR OR L...

Page 28: ...CTED TO EARTH GROUND AT THE SAME POINT TO AVOID CIRCULATING GROUND CURRENTS NOTE 2 DIODE ADDED LOCAL TO INDUCTIVE LOAD TO SHUNT THE REVERSE EMF THAT IS GENERATED WHEN CURRENT THROUGH THE INDUCTOR RELA...

Reviews: