background image

       BusWorks

  

Model 903MB/902MB/901MB Network I/O Module User’s Manual                                         Digital I/O 

       ___________________________________________________________________________________________ 

- 16 - 

The following sections guide you 
through the Configuration Program 
property sheets used to configure 
90xMB I/O Modules.  Because these 
units perform simple digital I/O, 
configuration is simplified.  Property 
sheets vary slightly between models.  
Refer to on-line Help if you have trouble 
understanding parameters unique to 
your module. 

 
Starting The Program 

 
After clicking on the Series 900MB 
program icon to boot the Configuration 
Program, a screen will be displayed 
similar to that shown at right. 
 
To begin, click on the “Settings-Serial 
Communications…” pull-down menu (or 
press Ctrl-E) to set the COM port, baud 
rate, parity, and slave address that the 
host computer will use to communicate 
with the module.  Optionally, you can 
check the “Update Communications 
settings at download” box to 
automatically change the host settings 
to match the module if new settings are 
later downloaded to the module 
(recommended to conveniently maintain 
communication with a module following 
reconfiguration). 
 

                                                                                                 

                 

 

Available menu selections are listed below.                               COM Port    MODULE 
 
 

Note that the host COM port 
selected is indicated in the first 
box of the lower right-hand 
corner.  MODULE is indicated in 
the third box if a connected 
module is detected by the 
software.  The fourth and fifth 
boxes indicate NUM for Num lock 
and CAP for Caps lock, 
respectively. 

 
File 

New… 
Open… 
Save 
Save As… 
Print… 
Print Preview 
Print Setup… 

Recent File Indicated 

Exit

 

 
Use 

File-New

 to create a new 

configuration file.  You will be 
prompted to select a model 
number.  Use 

File-Open

 to open 

an existing configuration file. 
 
Use 

File-Save

 to save the 

current configuration file to disk.  
Use 

File-Save As

 to save the 

current configuration file to a new 
file name. 

Use 

File-Print

 to get a printout of 

the currently loaded configuration 
file.  Use 

File-Print Preview

 to 

view the current configuration or 
preview the print documentation.  
Use 

File-Print Setup

 to select a 

printer and font style. 

 
Module 

Upload Configuration 
Download Configuration 

 
Use 

Module-Upload 

Configuration

 to upload the 

module’s current configuration 
and calibration.  Use 

Module-

Download Configuration

 to 

write the currently loaded 
configuration to the module. 
 

Settings- 

Serial Communications… 

Communications Port 
Host Baud Rate 
Host Parity 
Slave Address 

 
Use the 

Communications Port

 

scroll window to select the host 
COM port the module is 
connected to (COM1-COM4), or 
type in a COM port as required, 
from COM1 to COM99. 

The selected COM port is 
indicated in the lower right hand 
corner of the screen. 
 
Use the 

Baud Rate 

scroll window 

to select the baud rate to be used 
by the host in communicating 
with the module. 
 
Use the 

Parity

 scroll window to 

select Odd, Even, or No Parity 
checking by the software for data 
transfer. 
 
Use the 

Slave Address

 scroll 

window to tell the software which 
module to address. 
 
If you wish to maintain 
communications with a module 
following download, check the 

“Update Communications 
settings at download”

 box of 

the Settings window to keep the 
host in synch with a module if the 
module settings are changed. 
 
If the module is in Default Mode 
(indicated via a flashing status 
LED), the baud rate, address, & 
parity assumed by the module  

are fixed at 9600bps, 247, & No 
Parity.  You must use the same 
settings as the connected 
module. 

 
Help 

Configuration Help Topics 

Your Model

 Help Topics 

About Modbus Configuration 
About 

Your Model

 

 
Use 

Help

 to obtain information 

about using this software or 
configuring transmitters.  Note 
that context sensitive help (

?) is 

also available for help on a 
specific field or topic.  Simply 
click on the [

?] button, then click 

on the field or topic of interest to 
obtain help on that subject.  You 
may also click the right mouse 
button to copy or print the help 
screen while it is being displayed. 
 
The following sections review the 
configuration of a Model  
903MB-0900 transmitter module.  
Configuration of your model will 
be similar. 
 

Summary of Contents for 901MB

Page 1: ...t With Sinking Outputs And Active Low Inputs USER S MANUAL ACROMAG INCORPORATED 30765 South Wixom Road P O BOX 437 Wixom MI 48393 7037 U S A Tel 248 295 0880 Fax 248 624 9234 Copyright 2000 Acromag In...

Page 2: ...ning any type of control or monitoring system This is especially important where economic property loss or human life is involved It is important that the user employ satisfactory overall system desig...

Page 3: ...m with open drain outputs for convenient loopback monitoring of the output state High Speed Data Rates Supports half duplex RS485 baud rates up to 115K baud Key 903MB Module Features continued Conveni...

Page 4: ...LE INSTALLATION This transmitter module is packaged in a general purpose plastic enclosure Use an auxiliary enclosure to protect the unit in unfavorable environments or vulnerable locations or to main...

Page 5: ...ck wire insulation 1 4 inch on each lead before installing into the terminal block Since common mode voltages can exist on signal wiring adequate wire insulation should be used and proper wiring pract...

Page 6: ...s not require advanced familiarity with the Modbus protocol REGISTER MAP Modbus registers are organized into the following reference types identified by the leading number of the reference address Ref...

Page 7: ...bps Default 3 14400bps 4 19200bps 5 28800bps 6 38400bps 7 57600bps 8 76800bps 9 115200bps 40003 2 0002 Parity Default 0 None 0 None 1 or 2 stop bits 1 Odd Parity Checking 2 Even Parity Checking Model...

Page 8: ...mapping mirroring to the Holding Register space The format of the registers are identical and you only need to offset your address by 43000 For example if you want to read Input Register 1 through the...

Page 9: ...itional stop bit is normally transmitted to fill out the character frame for no parity Acromag units will accept one or two stop bits with no parity Modbus Addresses The master device addresses a spec...

Page 10: ...s Example Response Field Name Example Value Hex Slave Address 247 F7 Function Code 1 01 Byte Count 2 02 Data Coils 7 0 170 AA Data Coils 11 08 10 0A Error Check LRC or CRC To summarize the status of c...

Page 11: ...mmarize the contents of register 40001 two bytes is slave address 247 00F7H The contents of register 40002 two bytes is the baud rate setting 2 9600bps The contents of register 40003 is the parity set...

Page 12: ...t No response is returned to broadcast queries from a master device Force Multiple Coils 15 902MB 903MB Models Only This command will simultaneously force a sequence of coils 0x reference addresses ei...

Page 13: ...ta High Third Reg 0 00 Preset Data Low Third Reg 2 02 Error Check LRC or CRC Preset Multiple Registers Example Response Field Name Example Value Hex Slave Address 247 F7 Function Code 16 10 Starting R...

Page 14: ...6 bit signed integer value representing an A D count a DAC count or a time value with a range of 32768 to 32767 Percentage A 16 bit signed integer value with resolution of 0 005 lsb 20000 is used to r...

Page 15: ...nt a timeout error from occurring in the master 06 Slave Device Busy The slave is engaged in processing a long duration program command The master should retransmit the message later when the slave is...

Page 16: ...tly loaded configuration file Use File Print Preview to view the current configuration or preview the print documentation Use File Print Setup to select a printer and font style Module Upload Configur...

Page 17: ...g download Select from 1 to 247 Address 247 is reserved for Default Mode Use the Baud Rate scroll bar to select a new baud rate to be used by the module following download Select 2400 4800 9600 Defaul...

Page 18: ...k monitoring of the output state The source leads of each port output channel are tied in common to the port return lead RTN The drain leads are pulled up to the port excitation terminal via resistor...

Page 19: ...f each module Please refer to Acromag s Service Policy Bulletin or contact Acromag for complete details on how to obtain service parts and repair PRELIMINARY SERVICE PROCEDURE Before beginning repair...

Page 20: ...only Observe proper polarity Inputs include transient suppression devices and series connected 100K resistors plus diode over voltage clamps to the internal 5V supply Sockets are provided for installa...

Page 21: ...vision 2 Groups A B C D Consult Factory ENVIRONMENTAL SPECIFICATIONS Operating Temperature 25 C to 70 C 13 F to 158 F Storage Temperature 40 C to 85 C 40 F to 185 F Relative Humidity 5 to 95 non conde...

Page 22: ...ect outside of Default Mode until a software or power on reset has occurred Watchdog Timer A hardware watchdog timer is built into the microcontroller that causes it to initiate a self reset if the co...

Page 23: ...cation flag bits 2 0 of the Module Status register will be set if any of the port output channels have not been written to over the specified time period or if any of the port input channels have not...

Page 24: ...EXC1 100K SIP RES SOCKET INPUT BUFFER CONTROLS MULTIPLEXER 5V 5V 5V MICRO 100K 100K 5V STATUS LED 100K 100K 100K 100K INTEGRATED OUTPUT CONTROLS 5V PWR LED DEFAULT MODE SWITCH PUSH FOR DEFAULT MODE U...

Page 25: ...5 CH 3 42 CH 8 TB2 TB2 21 EXC2 23 CH 5 34 D 24 26 RTN 31 COM TB4 PWR D B A TB3 TB4 PWR D TB3 RS232 PORT COM 11 12 CJC 0 45 RTN OUT3 TB1 15 IN1 TB2 42 OUT1 TB3 COM TB2 23 26 25 IN2 IN3 IN3 INPUTS 2 3 3...

Page 26: ...FLASHES IN DEFAULT MODE PUSH FOR DEFAULT MODE DFT 9 8 7 6 ON WHEN OUTPUT CONDUCTING OR WHEN INPUT LOW DIGITAL CHANNELS STATUS LED YELLOW RUN PWR LED GREEN TB4 ST RUN Acromag DEFAULT MODE SWITCH SHIELD...

Page 27: ...OUTPUT IS OFF 0 FOR INPUT ONLY UNITS MODEL 901MB 0900 902MB 0900 903MB 0900 PAGE 3 OF 4 ELECTRICAL CONNECTIONS LED V 902MB 903MB OFF ON TO OTHER 3 CHAN OF PORT 100K I O RTN SOLID STATE RELAY SSR OR L...

Page 28: ...CTED TO EARTH GROUND AT THE SAME POINT TO AVOID CIRCULATING GROUND CURRENTS NOTE 2 DIODE ADDED LOCAL TO INDUCTIVE LOAD TO SHUNT THE REVERSE EMF THAT IS GENERATED WHEN CURRENT THROUGH THE INDUCTOR RELA...

Reviews: