3 Reference standards
3.1 IEC 60364-7-710:2002
Electrical installations of buildings - Part 7-710: Requirements for special installations
or locations - Medical locations
3.2 IEC62020-1:2020
Electrical accessories - Residual current monitors (RCMs) - Part 1: RCMs for household and
similar uses
4 Technical parameters
4.1 Technical parameters of AIM-R100
They are shown in Table 2.
Table 2 Parameters of AIM-R100 residual current monitor
Items
parameters
Accessory
power supply
Voltage
AC 220V±10%
Power
dissipation
≤
3VA
Residual
current
monitoring
Loops
12
Measure range
0~5000mA
Setting range
6~1000mA
Frequency
50±5 Hz
Relay output
output
1 relay output, normally open
Contact
capacity
AC 250V/3A DC 30V/3A
Communicatio
n
Interface
RS485
Protocol
Modbus-RTU
MTBF
≥
50000 hour
4.2 Technical parameters of AID150
They are shown in Table 3.
Table 3 Technical parameters of AID150 centralized alarm and display instrument
Items
parameters
Accessory
power supply
Voltage
DC 24V
Power
dissipation
< 0.6W
Residual current display range
×