![Acrel AIM-R100 Installation And Operation Manual Download Page 20](http://html1.mh-extra.com/html/acrel/aim-r100/aim-r100_installation-and-operation-manual_2841066020.webp)
17
loop 3 state (Same as above)
2bit
loop 4 state (Same as above)
2bit
13
000CH
Fault Flag
R
loop 5 state (Same as above)
2bit
loop 6 state (Same as above)
2bit
loop 7 state (Same as above)
2bit
loop 8 state (Same as above)
2bit
loop 9 state (Same as above)
2bit
loop 10state (Same as above)
2bit
loop 11 state (Same as above)
2bit
loop 12 state (Same as above)
2bit
14
000DH
SOE
1
Fault loop
R
1~12
u16
15
000EH
Fault value
R
10~5000
(0xE5E5 for short current
,
0xFAFA for break line)
u16
16
000FH
Threshold value
R
10~1000mA
u16
17
0010H
Fault-year
R
1~99
u8
Fault-month
R
1~12
u8
18
0011H
Fault-day
R
1~31
u8
Fault-hour
R
0~23
u8
19
0012H
Fault-minute
R
0~59
u8
Fault-second
R
0~59
u8
20~73
0013H-
0048H
SOE 2~10
R
Format is same as SOE 1
74
0049
Reserved
u16
75~86
004AH~
0055H
loop 1~12 residual current
value
R
0~5000mA
u16*12
87~98
0056H~
0061H
Loop 1~12 alarm value
R/W
6~1000mA
u16*12