7.3 AIM-R100 communication address table
NO. Address
parameters
Read/write
Range
Data Type
1
0000H
Password
R/W
0001~9999; default 0001
u16
2
0001H
Address
R/W
1~16; default 1
u8
Baud Rate
R/W
1~3:4800,9600,19200bps; default 2
u8
3
0002H
Reserved
u16
4
0003H
Reserved
u16
5
0004H
RTC-year
R/W
1~99
u8
RTC-month
R/W
1~12
u8
6
0005H
RTC-day
R/W
1~31
u8
Reserved
u8
7
0006H
RTC-hour
R/W
0~23
u8
RTC-minute
R/W
0~59
u8
8
0007H
RTC-second
R/W
0~59
u8
Reserved
u8
9
0008H
Tripping time
R/W
0~60s
,
default 6s
u16
10~11
0009H~
000AH
Reserved
u16*2
12
000BH
Meter type
R
bit15~bit12
,
0 is insulation monitor
,
1 is residual
current monitor
4bit
Reserved
bit11-bit8
4bit
Fault Flag
R
loop 1 state
(00 normal, 01 short circuit, 10 break line, 11 overload)
2bit
loop 2 state (Same as above)
2bit