![Acrel AIM-R100 Installation And Operation Manual Download Page 13](http://html1.mh-extra.com/html/acrel/aim-r100/aim-r100_installation-and-operation-manual_2841066013.webp)
10
passes through four wires A, B, C and N. Residual current transformer output lines connected to the
corresponding terminal of AIM-R100, connecting to 100Ω resistance to empty terminal to avoid causing false
alarms.
(5) terminal 15, 16 of the AIM-R100 residual current monitor and Terminals A and B of AID150 centralized
alarm and display instrument can be connected with 2x1.5 mm
2
shielded twisted-pair cable. When AID150
centralized alarm and display is used to monitor multiple AIM - R100, the connection mode of the communication
line should be hand in hand (A to A, B to B, one by one), RS485 bus between the end of the first two
communication terminal should be matches with a resistance, recommend and appendant resistance is 120 Ω.
5.5 Matters needing attention
(1) The residual current monitoring products, except for the AID150 centralized alarm and display
instrument, should be centrally installed in the isolated power cabinet or distribution cabinet. centralized alarm
and display instrument generally select wall installation.
(2) During installation and wiring, the wiring diagram shall be strictly followed. It is better to press and
connect the wiring with the needle-type sleeve joint, then insert the corresponding terminals of the instrument and
tighten the screws to avoid abnormal working of the instrument due to poor contact.
(3) the empty loop of AIM-R100 must be connected to 100Ω resistance, avoid the break line fault alarm.
6
Operation and Usage
6.1 Panel
AIM-R100 residual current monitor panel
6.2 LED
instructions
6.2.1 AIM-R100
residual current monitor LED instruction
LED states
instruction
“RUN”
In normal operation, the light flashes at a frequency of about once a second
“COMM”
Communication status of the device. the indicator light flashes while
communication.
On
Comm
Fault
Alarm
Medical Residual Current Monitor
Menu/
Test/Esc
Product type
LCD screen
Indicators
Key
Acrel
AIM-M100
Acrel
AIM-M100
Acrel
AIM-M100
Acrel
AIM-M100
Acrel
AIM-M100
Acrel
Acrel
AIM-M100
Acrel
AIM-M100
Acrel
AIM-M100
Acrel
AIM-M100
Acrel
AIM-M100
Acrel
AIM-R100