17
KOOLMASTER PP20-VS2 rev.00
KOOLMASTER PP20-VS2
4.9. Clean Mode
The clean mode is used to interrupt regular
operations of the controller when the room is
empty. When this mode is enabled, the con-
troller closes all tunnel doors and curtains and
then only provides a minimum level of heat
and ventilation (optional). If minimum ventila-
tion is used in the clean mode, all inlets will
open to their respective minimum ventilation
position; otherwise they remain closed. The
letters
“CLn”
are shown on the LED display
when the clean mode is active.
Cleaning the room:
A soaking output can be
activated to clean up the room. If this output
is used, soaking cycles automatically start
when the clean mode is on. Refer to chapter
11 of this manual to get further information
about the soaking output.
Clean mode set point:
In clean mode, fans
that are used to provide minimum ventilation
and heaters operate according to the clean
mode set point: heaters turn on when the
room temperature is lower than the clean
mode set point and fans turn on when the
temperature is higher than the set point.
Refer to section 5.1 to adjust the clean mode
set point.
Low temperature alarm:
The controller can
sound an alarm if the temperature gets too
low while the controller is in clean mode. Re-
fer to section 12.3 to set this alarm limit.
Select:
1.
Current Conditions (Main Menu)
Clean Mode
* A password may be required to access this menu.
Clean Mode
Clean Mode SetPoint
45.0 °F
Clean Mode Status:
Off
End of Clean Delay:
15 min
Use Min Ventilation ?
No
Detect Lo Temperature?
Yes
Set the following parameters:
2.
Clean mode set point —
Select what is the
target room temperature while the controller
operates in clean mode.
Clean mode status —
Select
“On”
to enable
the clean mode; select
“Off”
to disable it.
End of clean delay —
At the end of the clean
mode, the controller waits for a certain time
before monitoring temperature alarms again.
Specify the time required for the room tem-
perature to get back to normal or select
“Off”
to disable this function (decrease the param-
eter value until letters
“Off”
are displayed).
Use minimum ventilation? —
Select
“Yes”
to
activate minimum ventilation cycles while the
clean mode is on.
Detect low temperature? —
Select
“Yes”
to
enable the low temperature alarm limit or
select
“No”
to disable this alarm condition.
4.10. Test Mode
The test mode is used to simulate temperature
and relative humidity changes and to verify
the controller’s performances. When it is
enabled, all outputs of the controller operate
according to the simulated inside and outside
temperature and according to the simulated
level of relative humidity.
Select:
1.
Current Conditions (Main Menu)
Setup *
Test Mode
* A password may be required to access this menu.
Test mode
Test Mode
Off
Temperature
72.3 °F
Outside T°
-40.0 °F
Inside Humidity
40 %
Set the following parameters:
2.
Test Mode —
Switch on the test mode status
then set the simulated inside & outside tem-
perature and the humidity level. *
The outside
temperature and inside humidity factors are only
accessible if an outside temperature sensor and
humidity sensor are enabled (see sec. 4.7.1)
The test automatically ends after 15 min-
utes of inactivity. It can also end sooner
by switching the test mode status back
to
“Off”
.
4.11. Version
This menu shows the version number of your
controller program. This piece of information
is useful to get technical support.
Select:
1.
Current Conditions (Main Menu)
Setup *
User
Version
* A password may be required to access this menu.
KOOLMASTER PP20-VS2
SOFTWARE
VX.X
FIRMWARE
VX.X