Installation & Operation Manual - Model AVR6000
Contents of this Manual are Subject to Change Without Notification
Page 24
6.5.3.1.1.1
Setpoint Configuration Glossary of Terms
Min Supply Airflow Setpoint:
This is the minimum supply air setpoint for the
AVR6000 supply valve. This value is usually based on the minimum air change rate
(ACH) for each setpoint mode.
Max Heating Supply Airflow Setpoint:
This is the maximum supply airflow setpoint
that will be used during the second stage of heating. This value is only used for
applications that implement the dual max logic control logic. This value is ignored
for applications that do not implement dual max control logic.
Max Supply Airflow Setpoint:
This is the maximum supply airflow setpoint that will
be used all tracking scenarios.
Max General Exhaust Airflow Setpoint:
This is the maximum GE/Return airflow
setpoint that will be used for all tracking scenarios.
Minimum General Exhaust Airflow Setpoint:
This is the minimum GE/Return airflow
setpoint that will be used for all tracking scenarios.
Room Offset Airflow Setpoint:
This is the setpoint for the airflow offset between
the supply airflow and total exhaust that is required to achieve the desired
pressurization. Negative room offset values are used to maintain negatively
pressurized spaces and positive room offset values are used to maintain positively
pressurized spaces.
Room Temperature Heating Setpoint:
This is the temperature setpoint used as a
threshold for activating the room temperature heating control loop.
Room Temperature Cooling Setpoint:
This is the temperature setpoint used as a
threshold for activating the room temperature cooling control loop.
Min Discharge Temperature Setpoint:
This is the low setpoint limit for the supply
discharge air temperature control.
Max Discharge Temperature Setpoint:
This is the high setpoint limit for the supply
discharge air temperature control.
6.5.3.1.2
ARS Select Configuration
All AVR applications require the room temperature measurement is provided by
either Accutrol model ARS or ADS which is connected to the Device Port on the
AVR6000 controller. The ARS is a wall-mount room temperature sensor that can be
ordered from the factory with different options therefore requires field
configuration. The ADS is a duct-mount return air temperature sensor which does
not require field configuration.
2 ARS Select Configuration
Note:
Before proceeding, verify which
ARS model connected to the AVR6000. For
applications that use the ADS return air duct
temp sensor, this menu item is not active.