5.3.1
Cable Specifications
AVR CONNECTION
CABLE TYPE
NOTES
24V POWER
16-18 AWG, 2-conductor
1
ANALOG INPUTS
18-22 AWG, shielded twisted pair
DRY CONTACT INPUTS 18-22 AWG, twisted pair
ANALOG OUTPUTS
18-22 AWG, shielded twisted pair
RELAY OUTPUTS
18-22 AWG, twisted pair
BACnet MS/TP
22-24 AWG, shielded twisted pair, low cap.
2
DEVICE PORT
factory cable provided with ARS or ADS
ACCUNET NETWORK 22-24 AWG, shielded twisted pair, low cap.
2
CABLE SPECIFICATIONS
5.3.2
Wiring Diagram Notes
1. POWER WIRING
Consult local building codes and project specifications for wiring requirements.
CAUTION: Maintain power source polarity otherwise equipment may be
damaged.
WARNING: Switch or circuit breaker must be included in the installation and
located where it is easily reached and marked as a disconnecting device for the
equipment. Power source must be current limited to less than 8-amps.
2. COMMUNICATIONS WIRING
Cable Type; Use low-capacitance cable, Windy City Wire # 042002 or equivalent
for BACnet and AccuNet wiring.
Termination; Install 120-ohm resistors /- terminals on the first & last
device on network segment. Failure to do so will result in unreliable
communications.
Ground; the cable shield shall be grounded at one end of the network segment
only.