5. Preset Multiple Registers (Function Code 16)
Query
Function Code 16(10H Hex) allows the user to modify the contents of multiple registers.
AcuDC 240 system parameters can be written by this function code.
The following example depicts how to preset slave device 1's AO1 parameter (current),
lower limit sign (+), lower limit value (0%), upper limit sign (+), upper limit value (100%).
Addr Fun
Data start
reg hi
Data start reg
lo
Data #of
reg hi
Data #of
reg lo
Byte
count
Value1
hi
Value1
lo
01H
10H
01H
09H
00H
05H
0AH
00H
01H
Value2
hi
Value2
lo
Value3
hi
Value3
lo
Value4
hi
Value4
lo
Value5
hi
Value5
lo
CRC16
hi
CRC16
lo
00H
00H
00H
00H
00H
00H
00H
64H
C5H
8AH
Table 4-12 Preset multiple registers query frame
Response
The correct response is to send back address, function code, data starting address, data
number, CRC check after the value is changed .
Addr
Fun
Data start
reg hi
Data start reg
lo
Data #of reg
hi
Data#of
reg lo
CRC16 hi
CRC16
lo
01H
10H
01H
09H
00H
05H
D1H
F4H
Table 4-13 Preset multiple registers response
4.3 AcuDC 240 Communication Address Table
Basic Measurement Parameter Address
Use Function Code 03 to read.
Summary of Contents for AcuDC 241
Page 1: ...AcuDC 240 Series Power Meter User s Manual...
Page 2: ......
Page 6: ...IV...
Page 8: ...VI...
Page 9: ...1 Chapter 1 Introduction 1 1 Meter Overview 1 2 Area of Application 1 3 AcuDC 240 Series...
Page 12: ...4...
Page 13: ...5 Chapter 2 Installation 2 1 Appearance and Dimensions 2 2 Installation Methods 2 3 Wiring...
Page 48: ...40...
Page 69: ...61 Appendix C Version Information Version Data Description V1 01 20120723 1st version...