30
4
th
screen: full range current setting. Range: 20-50000, unit is
A. Press “F” and “V/A”to edit the vaule. Press “V/A”at the last
digit to go to the next screen.
Note: only indirect current wiring has this screen.
5
th
screen: full range shunt setting. Range: 50-100, unit is mV.
Press “F” and “V/A”to edit the vaule. Press “V/A”at the last digit
to go to the next screen.
Note: only the current wiring via external shunt has this
screen.
6
th
screen: current hall effect sensor setting. Two modes: 0:0
- ±5V/4 - 20mA. 1:0 - ±4V/4-12-20mA. Press "F" key to select.
Press “V/A” to go to the next screen.
Note: only the current wiring via current hall effect sensor
has this screen.
7
th
screen: full range voltage setting. Range: 5-1200, unit is V.
Press “F” and “V/A”to edit the vaule. Press “V/A”at the last digit
to go to the next screen.
Figure
3-14
full range current setting
Figure
3-15
full range shunt setting
Figure
3-16
current hall effect sensor setting
Figure
3-17
full range voltage setting