2. Read DI status (Function Code 02)
This function allows the user to obtain DI status ON/OFF(1 = ON , 0 = OFF). On top of slave
device address and function code, query frame must contain the digital input register,
starting address and the number of registers to be read. AcuDC 240 DI address starts from
0000H(DI1=0000H,DI2=0001H)
Table 4.6 depicts of reading DI1 to DI2 status of the slave device with the address of 17.
Addr
Fun
DI start
addr hi
DI start
addr lo
DI num hi
DI num lo
CRC16 hi
CRC16 lo
11H
02H
00H
00H
00H
02H
FBH
5BH
Table 4-6 Query frame of reading DI status
Response
The slave device anwsers the master device's query. The response frame contains slave de-
vice address, function code, data quantity and CRC check. Each DI utilizes one bit(1 = ON ,
0 = OFF). Table 4.7 depicts the response frame.