51
Address
Parameter
Data Type
Property
0200H
,
0201H
Voltage
Float
R
0202H
,
0203H
Current
Float
R
0204H
,
0205H
Power
Float
R
0206H
,
0207H
AO1
Float
R
0208H
,
0209H
AO2
Float
R
Table 4-14 Real-time measurement address table
Note:The high byte is followed by the low byte.
Running time
The data space below is for running time;
Function code: 03 Read.
Address
Parameter
Range
Data Type
Property
0280H
0281H
Meter running time
0~999999999
long
R
0282H
0283H
Load running time
0~999999999
long
R
Energy
The data space below is for energy;
Function code: 03 Read; 16: Write;
Address
Parameter
Range
Data Type
Property
0300H
0301H
Export energy
0~999999999
long
R/W
0302H
0303H
Import energy
0~999999999
long
R/W
0304H
0305H
Total energy
0~999999999
long
R/W
0306H
0307H
Net energy
0~±999999999
long
R/W
The relationship between the register value and the real value. (Rx is the register value)
Summary of Contents for AcuDC 241
Page 1: ...AcuDC 240 Series Power Meter User s Manual...
Page 2: ......
Page 6: ...IV...
Page 8: ...VI...
Page 9: ...1 Chapter 1 Introduction 1 1 Meter Overview 1 2 Area of Application 1 3 AcuDC 240 Series...
Page 12: ...4...
Page 13: ...5 Chapter 2 Installation 2 1 Appearance and Dimensions 2 2 Installation Methods 2 3 Wiring...
Page 48: ...40...
Page 69: ...61 Appendix C Version Information Version Data Description V1 01 20120723 1st version...