46
Data start reg hi: Start register address, high byte
Data start reg lo: Start register address, low byte
Data #of reg hi: Number of registers, high byte
Data #of reg lo: Number of registers, low byte
CRC16 hi: CRC high byte
CRC16 lo: CRC low byte
1. Read Relay Output Status(Function Code 01)
Query
The master device sends query frame to the salve deivce. Function Code 01 allows users
to acquire the relay output status (1=ON, 0=OFF) of the slave device with the specified
address. Along with slave device address and function code, query frame must contain the
relay register starting address and the number of registers to be read.
AcuDC 240 relay output address starts from 0000H(Relay1=0000H,Relay2=0001H)
Table 4.4 depicts reading Relay 1 and Relay 2 status from slave address 17.
Addr
Fun
DO start
reg hi
DO start reg
lo
DO #of regs
hi
DO #of regs
lo
CRC16
Hi
CRC16
Lo
11H
01H
00H
00H
00H
02H
BFH
5BH
Table 4-4 Query frame of reading Relay Output status
Response
The slave device anwsers the master device's query. The response frame contains slave
device address, function code, data quantity and CRC check. Each relay utilizes one bit(1 =
ON , 0 = OFF). Table 4-5 depicts the response frame.
Summary of Contents for AcuDC 241
Page 1: ...AcuDC 240 Series Power Meter User s Manual...
Page 2: ......
Page 6: ...IV...
Page 8: ...VI...
Page 9: ...1 Chapter 1 Introduction 1 1 Meter Overview 1 2 Area of Application 1 3 AcuDC 240 Series...
Page 12: ...4...
Page 13: ...5 Chapter 2 Installation 2 1 Appearance and Dimensions 2 2 Installation Methods 2 3 Wiring...
Page 48: ...40...
Page 69: ...61 Appendix C Version Information Version Data Description V1 01 20120723 1st version...