Troubleshooting
TS30: PFC module protection diagnosis and solution
Description
: When the voltage signal that IPM send to compressor drive chip is abnormal, the LED displays the failure
code and the AC turns off.
Recommended parts to prepare:
• Connection wires
• Inductance
• Outdoor main PCB
• PFC module
Troubleshooting and repair:
At first test the resistance between every two ports of U, V, W of IPM and P, N. If any result of them is 0 or close to 0, the
IPM is defective. Otherwise, please follow the procedure below:
Check whether the
connecting line between
main board and the PFC
module is connected tightly
Check whether the
connecting line between
main board and the PFC
module is connected tightly
Yes
Measure whether the voltage
between P and N is normal
refer to the Index
?
Measure whether the voltage
between P and N is normal
refer to the Index
?
No
Check whether the
inductance of PFC module is
good? If the inductance is
good, the resistance of the
two ports is 0
Check whether the
inductance of PFC module is
good? If the inductance is
good, the resistance of the
two ports is 0
Yes
Replace the inductance
Replace the inductance
No
Connect it tightly, check
normal or not
Connect it tightly, check
normal or not
Replace the outdoor main board
Replace the outdoor main board
Yes
Yes
No
No
Replace the PFC module
Replace the PFC module
Trouble is solved
Trouble is solved
45
Summary of Contents for COLONNA CLN130R
Page 3: ......
Page 6: ......
Page 7: ...Contents 1 Precautions 2 2 Information servicing For flammable materials 3 Safety Precautions...
Page 19: ...Specifications 7...
Page 20: ...Outdoor unit printed circuit board diagram 17122000041841 Specifications 8...
Page 22: ...Outdoor unit DC motor driver board diagram 17122000021912 5 6 1 2 3 4 Specifications 10...
Page 41: ...Indoor Unit Disassembly 2 1 Dimension...
Page 57: ...Outdoor Unit Disassembly 3 2 Dimension UECS130R...
Page 100: ...For some models 33...