TS33: Communication error between outdoor main chip and compressor driven chip
Troubleshooting
diagnosis and solution
Description
: The main chip cannot detect the compressor driven chip
Recommended parts to prepare:
• Outdoor main PCB
• Electric control box
Troubleshooting and repair:
Replace the electric control box
Replace the electric control box
Trouble is solved
Trouble is solved
YES
Shut off the power supply and
turn it on 2 minutes later.
Shut off the power supply and
turn it on 2 minutes later.
Is it still displaying
the error code?
Is it still displaying
the error code?
NO
Replace outdoor main board
Replace outdoor main board
If the system can run
normally?
If the system can run
normally?
NO
47